WX9 ASD Installation and Operation Manual
77
Preset Speed 3
Program
Frequency
Preset Speeds
This parameter assigns an output frequency to binary number 0011 and is
identified as
Preset Speed 3
. The binary number is applied to
S1
–
S4
of the
Control
Terminal Strip
to output the
Preset Speed
(see
for additional
information on this parameter).
Direct Access Number — F020
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0
Maximum — Upper-Limit Freq. (
Units — Hz
Preset Speed 4
Program
Frequency
Preset Speeds
This parameter assigns an output frequency to binary number 0100 and is
identified as
Preset Speed 4
. The binary number is applied to
S1
–
S4
of the
Control
Terminal Strip
to output the
Preset Speed
(see
for additional
information on this parameter).
Direct Access Number — F021
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0
Maximum — Upper-Limit Freq. (
Units — Hz
Preset Speed 5
Program
Frequency
Preset Speeds
This parameter assigns an output frequency to binary number 0101 and is
identified as
Preset Speed 5
. The binary number is applied to
S1
–
S4
of the
Control
Terminal Strip
to output the
Preset Speed
(see
for additional
information on this parameter).
Direct Access Number — F022
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0
Maximum — Upper-Limit Freq. (
Units — Hz
Preset Speed 6
Program
Frequency
Preset Speeds
This parameter assigns an output frequency to binary number 0110 and is
identified as
Preset Speed 6
. The binary number is applied to
S1
–
S4
of the
Control
Terminal Strip
to output the
Preset Speed
(see
for additional
information on this parameter).
Direct Access Number — F023
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0
Maximum — Upper-Limit Freq. (
Units — Hz
Preset Speed 7
Program
Frequency
Preset Speeds
This parameter assigns an output frequency to binary number 0111 and is
identified as
Preset Speed 7
. The binary number is applied to
S1
–
S4
of the
Control
Terminal Strip
to output the
Preset Speed
(see
for additional
information on this parameter).
Direct Access Number — F024
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0
Maximum — Upper-Limit Freq. (
Units — Hz
Low-Speed Signal Output Frequency
Program
Terminal
Reach Settings
The
Low-Speed Signal Output Frequency
parameter sets an ASD output
frequency threshold that activates the assigned discrete output terminal for the
duration that the ASD output speed is equal to or less than this setting.
Direct Access Number — F100
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — Upper-Limit Freq. (
Units — Hz
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......