Use and Maintenance Manual - Series V8 E V10 E
Page 42
90
243
PUMP VACC RANGE Pump control out of range
If the parameter EVP TYPE is set to ANALOG, acquire the
values LOWER MIN and MAX LOWER once again.
If the controller is in Combiacx configuration and the
parameter PROPORTION. LIFT is set to ON, acquire also
the values LIFT MIN and MAX LIFT once again.
91
214
EVP COIL OPEN Proportional solenoid valve coil -
open circuit
A) It is recommended checking the wiring in order to verify if
the coil of the proportional solenoid valve EVP is connected
correctly, without interruptions;
B) If the alarm continues to be present, even by connecting
the coil to the correct pin or replacing it, the problem is
inside the logic board of the controller and must be replaced.
92
236
CURRENT GAIN
The Parameters current Gain are
not set
Request the assistance of an AIRO technician to execute
the correct adjustment of the current gain parameters.
93
197
OVERRIDE
OVERRIDE mode
Warning notifying that you are operating in OVERRIDE
mode.
Turn off and then turn on the system in normal operation
mode, with the ground or platform controls, and check that
the warning is no longer present.
94
0
NONE
Misalignment between hour meter data of the controller and
that of the indicator.
Leave the machine on for more than 2 minutes to allow data
alignment.
95
244
HEIGHT LIMIT EXC Lifting sensor signal (optional)
over the allowed limit.
Warning notifying that the maximum set height limit of the lift
mast has been exceeded.
Lower the mast and check out if the warning disappears.
96
237
ANALOG INPUT
Analog signal conversion
problem
If the issue occurs permanently, the controller must be
replaced.
97
196
AUX RELE SHORTED Short circuit on auxiliary relay
coil
Check wiring of the auxiliary activation relay of the line
contactor LC.
If wiring is correct, there may be an error in the driver circuit
inside the controller.
98
219
PEV NOT OK
Positive voltage of solenoid
valves not correct
Check connector B2: it must be connected to battery voltage
(after the line contactor LC).
99
253
SLIP_PROFILE
SLIP profile parameter choice
error
Check the value of these parameters in the hardware setting
menu.
Below is a table that summarizes some tests carried out after removing the cables and/or connectors, with related messages
displayed on the indicator MDI.
Содержание Airo V Series
Страница 14: ...Use and Maintenance Manual Series V8 E V10 E Page 14...
Страница 17: ...Use and Maintenance Manual Series V8 E V10 E Page 17...
Страница 75: ...Use and Maintenance Manual Series V8 E V10 E Page 75...
Страница 94: ...Use and Maintenance Manual Series V8 E V10 E Page 94...
Страница 95: ...Use and Maintenance Manual Series V8 E V10 E Page 95...
Страница 96: ...Use and Maintenance Manual Series V8 E V10 E Page 96...
Страница 97: ...Use and Maintenance Manual Series V8 E V10 E Page 97...
Страница 98: ...Use and Maintenance Manual Series V8 E V10 E Page 98...
Страница 100: ...Use and Maintenance Manual Series V8 E V10 E Page 100...