5
、
Modbus communication example
Read the setting frequency of 1# Variable Frequency Drive, and the setting frequency of
Variable Frequency Drive response is 50.00Hz.
Start the 1# Variable Frequency Drive to rotate forward
Premises
Function
code
Register address
Register
content
Checksum
Request
0x01
0x06
0x8000
0x0001
0x61CA
Response
0x01
0x06
0x8000
0x0001
0x61CA
Premises
Funct
-ion
code
Register
address
Number
of
register
Number
of bytes
in
contents
Register
content
Checksum
Reque
-st
0x01
0x03
0x0000
0x0001
No
No
0x840A
Respo
nse
0x01
0x03
No
No
0x02
0x1388
0xB512