User Manual of TI10 Series Variable Frequency Drive
- 59 -
Fault
code
Failure
Display
Fault name
Cause
Countermeasure
Abnormal driving plate
Seek technical support
Abnormal module
Seek technical support
20
Er.LLd
Variable
Frequency
Drive output
Off load
The operating current of the
Variable Frequency Drive is
less than P30.07
Confirm whether the load is
disengaged or whether the
P30.07 and P30.08
parameter settings
conform to the actual
operating conditions.
21
Er.GdF
Variable
Frequency
Drive Short
circuit to
ground
Output wiring short circuit to
ground
Check motor wiring and
output impedance to
ground
Abnormal motor insulation
Check motor
Abnormal Variable
Frequency Drive module
Seek technical support
Large output current to floor
drain
Seek technical support
22
Er.EEP
EEPROM read
and write
Failure
Abnormal EEPROM
read-write
Seek technical support
23
Er.Sci
Communicatio-
n overtime fault
Improper setting of
communication baud rate
Correct setting
Disconnected wiring at
communication port
Reconnect
The upper computer is not
working
Make the upper computer
work
Communication parameter
error of Variable Frequency
Drive
Correct setting
Large interference on site
Check peripheral
equipment or seek services
24
Er.tPA
Reaching
power-on time
Accumulative power-on time
reaches the setting value.
Seek technical support
25
Er.trA
Reaching
running time
Accumulative running time
reaches the setting value.
Seek technical support
26
Er.rEF
PID given loss
PID given channel
Check given channel