User Manual of TI10 Series Variable Frequency Drive
- 51 -
Parameter
Name
Setting range
Factory value
Register
address
Properties
U01.01
Given
frequency at
the last fault
0.00Hz~300.00Hz
Actual value
0x8201
★
U01.02
Output
frequency at
the last fault
0.00Hz~300.00Hz
Actual value
0x8202
★
U01.03
Output Current
at the last fault
0.0A~6000.0A
Actual value
0x8203
★
U01.04
DC bus
voltage at the
last fault
0V~2000V
Actual value
0x8204
★
U01.05
Output Voltage
at the last fault
0V~2000V
Actual value
0x8205
★
U01.06
Input terminal
status of last
fault
00~F
Actual value
0x8206
★
U01.07
Output
terminal status
at the last fault
00~F
Actual value
0x8207
★
U01.08
Machine
running status
of the last fault
00~2F
Actual value
0x8208
★
U01.09
Radiator
temperature of
the last fault
0.0
℃
~120.0
℃
Actual value
0x8209
★
U01.10
Cumulative
running time of
the last fault
0.0h~6553.5h
Actual value
0x820A
★
U01.11
The last fault
code
0~100
Actual value
0x820B
★
U01.12
Given
frequency at
previous fault
0.00Hz~300.00Hz
Actual value
0x820C
★
U01.13
Output
frequency at
previous fault
0.00Hz~300.00Hz
Actual value
0x820D
★