![Thinkvert TI10 Series Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/thinkvert/ti10-series/ti10-series_user-manual_1107381030.webp)
User Manual of TI10 Series Variable Frequency Drive
- 23 -
Parameter
Name
Setting range
Factory value
Register
address
Properties
P11.17
FDT2 upper
level limit
P11.18~maximum
frequency
2.50Hz
0x1111
○
P11.18
FDT2 lower
level limit
0.00Hz~P11.17
2.00Hz
0x1112
○
P11.19
Frequency
arrival (FAR)
detection width
0.00Hz~maximum
frequency
2.50Hz
0x1113
○
P11.20
Zero frequency
signal
detection value
0.00Hz~maximum
frequency
0.50Hz
0x1114
○
P11.21
Zero frequency
return range
0.00Hz~maximum
frequency
0.00Hz
0x1115
○
P11.22
Zero current
detection level
0.0%~50.0%
5.0%
0x1116
○
P11.23
Zero current
detection time
0.00s~50.00s
0.50s
0x1117
○
P12 analog AI and high speed pulse HDI input
P12.00
AI analog
curve selection
Ones: AI1 characteristic
curve selection
Tens: AI2 characteristic
curve selection
0: no correction
1: curve 1(2 points)
2: curve 2 (4 points)
3: curve 3 (4 points)
00
0x1200
●
P12.01
Maximum
input of curve
1
Minimum input
(P12.03)~10.00V
10.00V
0x1201
○
P12.02
Maximum
input
corresponding
curve 1
-100.0%~100.0%
100.0%
0x1202
○