TI120 Series Variable Frequency Drive
Detailed parameter introduction
- 81 -
Output frequency
Jump frequency 1
Time
Jump range 1
Jump frequency 2
Jump frequency 3
Jump range 1
Jump range 2
Jump range 2
Jump range 3
Jump range 3
Figure 5-1 Schematic diagram of jumping frequency
P00.16
Inching frequency setting
range:0.00Hz~upper limit
frequency
Factory
default:5.00Hz
The setting frequency and inching acceleration/deceleration time during the inching operation are
determined by the function codes of P02.09 and P02.10.
P01 start and stop control parameters
P01.00
Given mode of running
command
range:0~4
Factory default:0
Select the input channel for the variable frequency drive control commands. The control commands
include: start, stop, forward, reverse, and inching.
0: keyboard command mode
The run command is controlled by the "Start" and "Stop" buttons on the keyboard panel. The "MON"
light on the keyboard is on.
1: terminal command mode
The run command is controlled by the switching value input terminal functions FWD, REV, FJOG,
RJOG, etc. The "MON" light on the keyboard is off.
2: Communication command mode
Start, stop, forward, reverse, and inching control of the variable frequency drive are carried out
through communication, please refer to Appendix A for related communication operations. The "MON"
light on the keyboard flashes.
3: multi-segment command mode
The run command is controlled by 1~multi-stage frequency terminal 4 of the switching value input
terminal function "multi-stage frequency terminal".
P01.01
Command given mode to
bundle frequency source
range:0x000~0xBBB
Factory default:000
This parameter is used for defining the use of bundling combination of run command and frequency