TI120 Series Variable Frequency Drive
Specification and Model Selection
- 144 -
Rated
frequency
50Hz/60Hz
Allowable
fluctuatio-
n range of
voltage
-15%~10%, actual allowable range: AC323V~528V
Allowable
fluctuatio-
n range of
frequency
±5%
Power
supply
capacity
(kVA)
5.0 6.7 12 17.5 22.8 33.4 42.8 45
54
52
63
81
97 127 150 179
Program
Technical specification
TI120-4TXXXG(B)
TI120-4TXXXL(B)
132 160 185 200 220 250 280 315 355 400 450 500 560 630 710
Adapted motor power
(kW)
132 160 185 200 220 250 280 315 355 400 450 500 560 630 710
Input
Rated
input
current
(A)
240 287 326 365 410 441 495 565 617 687 782 835 920 1050 1180
Output
Rated
output
current
(A)
260 305 350 377 426 465 520 585 650 725 810 900 1090 1100 1300
Output
Voltage
3-phase 0V~rated input voltage
Maximum
output
frequency
300.00Hz (modified by parameters)
Carrier
frequency
1.0 khz~16.0 KHz (carrier frequency can be automatically adjusted according to load
characteristics)
Overload
capacity
150% rated current 60s; 180% rated current 10s
;
; 200% rated current 0.5s
high
DC
reactor
Extern- Built-in
External option