TI120 Series Variable Frequency Drive
Detailed parameter introduction
- 94 -
command
Forward
inching
ON
OFF
Reverse
inching
OFF
ON
Stop
OFF
OFF
Stop
ON
ON
K2
K1
Xi FJOG
Xi RJOG
COM
H120
Figure 5-8 Schematic Diagram of Inching Command
5:3-wire operation
The above 1~5 functions are only valid under the terminal run command (P01.00=1); for the use of
three-wire operation, please refer to the description of the function code P10.11.
6: free stop
When the "free stop" terminal function is valid, the variable frequency drive shall stop freely.
7: emergency stop
When the "emergency stop" terminal function is valid, the variable frequency drive decelerates and
stops according to the time set in P02.08.
8: external stop
When the "external stop" terminal function is valid, the variable frequency drive stops according to
the setting stop mode.
9: operation forbidden
When the "run prohibited" terminal function is valid, the variable frequency drive does not receive
any start command and keeps stopping.
10: operation suspended
During the operation of the variable frequency drive, after the function of the "operation pause"
terminal is valid, the variable frequency drive runs at zero frequency. When the "operation pause"
terminal is invalid, the variable frequency drive resumes operation.
11: external fault input
After this function is valid, the variable frequency drive reports Er.EtE fault.
12: fault reset (RESET)
After the variable frequency drive fails, this function can be used for resetting the variable frequency
drive, which is the same as the Stop function on the keyboard.