TI120 Series Variable Frequency Drive
Detailed parameter introduction
- 104 -
P11.19
Frequency arrival (FAR)
detection width
range:0.00Hz~maximum
frequency
Factory
default:2.50Hz
It is used for detecting the deviation between the output frequency and the setting frequency; when
the deviation between the output frequency and the setting frequency is within the range of this function
code, and the output terminal is set to the "frequency reaching FAR" function, a valid signal is output.
Frequency reaching
detection width
Time
Output frequency
Output signal
Figure 5-14 Schematic Diagram of Frequency Reaching Detection
P11.20
Zero frequency signal
detection value
range:0.00Hz~maximum
frequency
Factory
default:0.50Hz
P11.21
Zero frequency return range
range:0.00Hz~maximum
frequency
Factory
default:0.00Hz
P11.22
Zero current detection level
range:0.0%~50.0%
Factory default:5.0%
P11.23
Zero current detection time
range:0.00s~50.00s
Factory
default:0.50s
The output terminal function is set to "zero current detection", when the variable frequency drive is
in the running status, and the output current is less than the setting level of P11.22, the duration is
greater than the time of P11.23, then a valid signal is output.
The zero current detection level is a percentage relative to the rated current of the variable
frequency drive.
P12 analog AI and high-speed pulse HDI input
P12.00
AI analog curve selection
range:0x00~0x33
Factory default:00
Ones: AI1 characteristic curve selection