TI120 Series Variable Frequency Drive
Parameter List
- 42 -
Parameter
Name
Setting range
Factory
default
Register address
Properties
P12.20
Minimum
input
corresponding
value of curve
3
-100.0%~100.0%
0.0%
0x1214
○
P12.21
AI1 input bias
-100.0%~100.0%
0.0%
0x1215
○
P12.22
AI1 input gain
-2.000~2.000
1.000
0x1216
○
P12.23
AI1 input
filtering time
0.000s~10.000s
0.050s
0x1217
○
P12.24
AI2 input bias
-100.0%~100.0%
0.0%
0x1218
○
P12.25
AI2 input gain
-2.000~2.000
1.000
0x1219
○
P12.26
AI2 input
filtering time
0.000s~10.000s
0.050s
0x121A
○
P12.33
HDI maximum
input
frequency
P12.35~100.00kHz
10.00kHz
0x1221
○
P12.34
HDI maximum
corresponding
value
-100.0%~100.0%
100.0%
0x1222
○
P12.35
HDI minimum
input
frequency
0.00kHz~P12.33
0.00kHz
0x1223
○
P12.36
HDI minimum
corresponding
value
-100.0%~100.0%
0.0%
0x1224
○
P12.37
HDI input
filtering time
0.000s~1.000s
0.001s
0x1225
○
P13 Analog AO and High Speed Pulse HDO Output
P13.00
AO1 terminal
output
function
selection
00: no output
01: setting frequency
02: output frequency
03: output current (relative
variable frequency drive)
04: output torque (absolute
value)
05: output voltage
06: bus voltage
07: output power
08: AI1 input
09: AI2 input
10: reserve
11: pulse input (0-50kHz)
12: motor current
13: output torque (relative
value)
14: torque command
2
0x1300
○