TI120 Series Variable Frequency Drive
Detailed parameter introduction
- 79 -
P00.06
Main and auxiliary overlay
selection of frequency
range:0x00~0x34
Factory default:00
Ones: frequency given mode
0: frequency main given
The frequency source is determined by P00.01 frequency main setting mode, please refer to
P00.01 parameter function code for details.
1: main and auxiliary operation result of frequency
The frequency setting is determined by the result of the main and auxiliary operations, and the
relationship between the main and auxiliary operations is determined by the ten-digit setting value of this
parameter.
2: main given and auxiliary given switching of frequency
The frequency source switching terminal can be input through the switching value, so that the
frequency main setting and frequency auxiliary setting can be switched. When the frequency source
switching terminal is invalid, the frequency main setting is used as the frequency setting source;
otherwise, the frequency auxiliary setting is used as the frequency setting source.
3: main given and main auxiliary operation result switching of frequency
The frequency source switching terminal can be input through the switching value, so that the
frequency main setting and main and auxiliary calculation results can be switched. When the frequency
source switching terminal is invalid, the frequency main setting is used as the frequency setting source;
otherwise, the main and auxiliary operation result is used as the frequency setting source.
4: auxiliary given and main auxiliary operation result switching of frequency
The frequency source switching terminal can be input through the switching value, so that the
frequency auxiliary setting and main and auxiliary calculation results can be switched. When the
frequency source switching terminal is invalid, the frequency auxiliary setting is used as the frequency
setting source; otherwise, the main and auxiliary operation result is used as the frequency setting
source.
Tens: given operation relation of frequency main and auxiliary
0: Min [main, auxiliary]
The smaller absolute value of the frequency main setting and the frequency auxiliary setting is
taken as the setting frequency, and the final result is limited by the upper and lower limits.
1: Max [main, auxiliary]
The greater absolute value of the frequency main setting and the frequency auxiliary setting is
taken as the setting frequency, and the final result is limited by the upper and lower limits.
2: Sub [main, auxiliary]
The result that the frequency main setting minuses the frequency auxiliary setting is used as the
setting frequency, and the final result is limited by the upper and lower limits.
3: Add [main, auxiliary]
The sum of the frequency main setting and the frequency auxiliary setting is used as the setting
frequency, and the final result is limited by the upper and lower limits.