Operating Instructions
67
Figure 58: Cool Test
When all tests are complete, the results are reported as PASS,
CHECK or FAIL (Figure 59). If the results are CHECK or
FAIL, the accompanying alarm codes will direct the technician
to the cause of the problem
Figure 59: Pretrip Pass
If the Pretrip Test results are CHECK or FAIL the problem
should be diagnosed and corrected before the unit is released
for service.
To return to the Main Menu press the EXIT Key. To return to
the Standard display press the EXIT Key again.
See summary of “Performing a Pretrip Tes displays in Figure
60 and Figure 61.