Alarm Codes
128
48
Check Belts/Clutch
If unit is shutdown, repair immediately. Otherwise, report alarm at
end of day.
X
49
Check Spare Sensor 1
Report alarm at end of day.
X
50
Reset Clock
Report alarm at end of day.
X
52
Check Heat Circuit
If unit is shutdown, repair immediately. Otherwise, report alarm at
end of day.
X
54
Test Mode Timeout
Clear alarm and restart unit.
X
56
Check Host Evap Fan Low Speed
If unit is shutdown, repair immediately. Otherwise, report alarm at
end of day.
X
57
Check Host Evap Fan High Speed
If unit is shutdown, repair immediately. Otherwise, report alarm at
end of day.
X
61
Low Battery Voltage
If unit is shutdown, repair immediately. Otherwise, report alarm at
end of day.
X
62
Ammeter Out of Calibration
If unit is shutdown, repair immediately. Otherwise, report alarm at
end of day.
X
Table of Alarm Codes (Continued)
Code Description
Operator Action
Level Of
Action
Ok
T
o
Run
Check
Sh
ut
Dow
n
Содержание Precedent C-600M
Страница 2: ......
Страница 58: ...Operating Instructions 56 Figure 44 Initiating a Manual Defrost Cycle Defrost Key...
Страница 62: ...Operating Instructions 60 Figure 50 Selecting Cycle Sentry or Continuous Mode Cycle Sentry Continuous Key...
Страница 71: ...Operating Instructions 69 Figure 61 Performing a Pretrip Test 2 From Figure 60...
Страница 85: ...Operating Instructions 83 Figure 83 Displaying and Clearing Alarm Codes 1 See Figure 84...
Страница 86: ...Operating Instructions 84 Figure 84 Displaying and Clearing Alarm Codes 2 From Figure 83...
Страница 164: ...162 CALIFORNIA Proposition 65 Warning Diesel exhaust is a chemical known to the State of California to cause cancer...
Страница 165: ......