Diagnosis: Troubleshooting, Warnings and Alarm Codes
228
05
Evaporator Coil Sensor Short Circuit
• When the sensor circuit resistance is lower than
602
Ω
.
• Indicates:
• Short circuit.
• Defective or wrong sensor.
• Defective wiring.
• Defective controller.
• Check for damaged sensor wires.
• Check sensor connections at controller.
• The sensor is a pt1000 – 2 wire sensor,
connected to the MP-4000 at connector J3 pin
5 and 6. CM-4000 upper left connector J3, 17
pin wide, pin number 1 is the right pin, seen at
the backside of the controller.
• The 2 sensor wires can be switched without
affecting the measurement.
• Disconnect the sensor, use an Ohm (
Ω
)
measuring device, measure the electrical
resistance between the two sensor wires.
The sensor can’t be examined without
disconnecting it.
The electrical resistance towards chassis must
be above meg ohm (M
Ω
) range.
• The sensor is a pt1000 – positive temperature
coefficient, which means that the electrical
resistance of the sensor increases with
temperature.
The sensor is defined to be 1000
Ω
@ 0°C.
Normal condition measuring with
disconnected sensor is 960
Ω
@-10°C,
1000
Ω
@0°C,1039
Ω
@+10°C, 1058
Ω
@+15°C,
1078
Ω
@+20°C.
The valid measuring limit for this pt1000
sensor is -100°C(602
Ω
) +75°C(approx
1300
Ω
).
06
Compressor Current Too High
• Occurs during pretrip (PTI) or function test only.
• During compressor test, if Compressor power
consumption is 25% above expected current draw
or compressor phase current level differs 33% or
more.
• If both alarm #6 and #7 is active this indicates too
high phase difference.
• Expected compressor current is a function of the
surrounding conditions.
• Indicates:
• Defective Digital Control valve.
• Defective compressor.
• Defective volt or amp meter on power module.
• Inaccurate ambient, condenser or evaporator
temperature measurement.
• Excessive condenser pressure due to air or
wrong refrigerant in system, or refrigerant over
charge
• Check evaporator and condenser sensor
temperatures for correct value (± 5 C [± 9 F])
by viewing Data menu.
• To determine the current draw measurement,
enter Manual Function Test menu. Start and
check current draw of the following
components separately and together:
compressor, compressor full loaded,
condenser fan and evaporator fan (high or
low).
• Check power supply volts on all 3 phases.
Alarm Codes, Descriptions and Corrective Actions (Continued)
Code
Description
Corrective Action
Содержание 098203
Страница 2: ......
Страница 3: ...MAGNUM TK 60275 4 MM Rev 3 08 15 Copyright 2012 Ingersoll Rand EMEIA Printed in Ireland...
Страница 193: ...Refrigeration Maintenance 191 Figure 163 Filter Drier...
Страница 200: ...Refrigeration Maintenance 198 Figure 169 Receiver Tank Figure 170 Water Cooled Condenser Tank...
Страница 257: ...255 Schematic Diagram RELEASED 19 Sep 2013...
Страница 258: ...256 Wiring Diagram Page 1 of 2 RELEASED 19 Sep 2013...
Страница 259: ...257 Wiring Diagram Page 2 of 2 RELEASED 19 Sep 2013...
Страница 263: ......