Controller Maintenance
150
Software File Format SIP
In version 3.0.0.0 we introduced the SIP file format for adding options like RMM to the unit.
Version 3.1.0.0 120612 and later were released in this SIP format.
CM4000_3.1.0.0.120612.srip.sip
In order to load version 3.1.0.0 or later software the MP4000 controller needs to have 3.0.0.0 software
installed first.
Load to SD Card file contains both 3.0.0.0 and 3.1.0.0 or later software.
If controller has 3.0.0.0 software installed, insert SD card to load 3.1.0.0 or later.
If controller has 2.5.4.0 or older software, insert SD to load 3.0.0.0 software. Then reinsert SD card to
load 3.1.0.0 or later software.
The MP4000 controller can be flashloaded using battery power or shore power. If the SD Card is not
configured correctly the MP4000 will display Command files not found.
Flashload Procedures Battery Power
1. Make sure that the unit is not active (no display).
2. Insert the SD card, with the latest software, into the slot on the side of the controller.
3. Activate the display using battery power by pushing the ON/OFF button. If the software on the SD
card is newer then what is on the controller, the upload will take place and progress can be shown on
the display.
4. When finished the display will shut down and the operation is finished.
Flashload Procedures Shore Power
1. Plug unit in and turn unit ON, let unit stabilize.
2. Insert SD card, with the latest software, into the slot on the side of the controller.
3. If the software on the SD card is newer then what is on the controller the display will show, PLEASE
WAIT… EXACTING COMMAND FILE, then UPDATE FIRMWARE, then PREPARING, then
UPDATING FIRMWARE 0-100%.
4. Once it show 100% unit will shut down and restart. Will show normal display and perform a AUTO
CONFIGRATION then normal start sequence.
5. Remove SD card and release unit.
NOTE: After completing the flashload check to make sure that the new Software/Application Revision
and Option File Revision have been loaded. If not, reinsert the SD card to load the Option File. If it is
still not showing the correct software revisions, turn controller OFF and back ON and recheck the
software revisions.
Содержание 098203
Страница 2: ......
Страница 3: ...MAGNUM TK 60275 4 MM Rev 3 08 15 Copyright 2012 Ingersoll Rand EMEIA Printed in Ireland...
Страница 193: ...Refrigeration Maintenance 191 Figure 163 Filter Drier...
Страница 200: ...Refrigeration Maintenance 198 Figure 169 Receiver Tank Figure 170 Water Cooled Condenser Tank...
Страница 257: ...255 Schematic Diagram RELEASED 19 Sep 2013...
Страница 258: ...256 Wiring Diagram Page 1 of 2 RELEASED 19 Sep 2013...
Страница 259: ...257 Wiring Diagram Page 2 of 2 RELEASED 19 Sep 2013...
Страница 263: ......