Diagnosis: Troubleshooting, Warnings and Alarm Codes
208
Troubleshooting Mechanical Problems
Condition
Possible Cause
Remedy
Compressor does not operate—
no amperage draw
Controller on; unit start sequence still
timing
Wait up to 2 minutes for compressor
start-up
No power to unit (condenser and
evaporator fans do not operate)
Locate fault and repair: power
source, power plug, CB1 main
circuit breaker, motor solid state,
motor terminals, motor, fuses on
power module
Open in 29 Vac control circuit
Check fuses and On/Off switch.
Replace or repair as required
Container temperature does not
demand compressor operation
Adjust controller setpoint
Compressor contactor inoperative
Replace compressor contactor
No output signal from controller
Diagnose and replace power
module or controller
Unit on defrost
Turn Unit On/Off switch Off and then
On again
Detective high pressure or low
pressure cutout switch
Replace defective switch
High condenser head pressure
causing high pressure cutout
Check refrigeration system and
correct fault
Defective compressor
Replace compressor
Controller shut unit down on
Compressor Over Temperature
Let compressor cool and controller
will reset automatically. Check vapor
injection valve and compressor
temperature sensor
Compressor motor internal thermal
overload protection open
If compressor contactor is
energized, wait 60 minutes for
protector to cool and reset.
Compressor does not operate—
excessive amperage draw or
intermittent cycling on overload
Rotating scroll stuck
Replace compressor
Seized or frozen compressor bearings Replace compressor
Improperly wired
Check/correct wiring against wiring
diagram
Low line voltage
Check line voltage — determine
location of voltage drop
Contacts in compressor contactor not
closing completely
Check by operating manually.
Repair or replace.
Open circuit in compressor motor
winding
Check motor stator connections.
Check stator winding for continuity.
If open, replace compressor
Defective compressor motor internal
thermal overload protector
Replace thermal overload protector
or compressor
Refrigerant overcharge or high side
restriction causing cycling on high
pressure cutout
Check for restricted filter drier,
in-line filter or high side; or
refrigerant overcharge
Inefficient condenser operation
causing cycling on high pressure
cutout
Check condenser airflow,
condenser fan motor, fan blade,
condenser grille, condenser coil
temperature sensor, water pressure
switch (option), water flow rate
(option) and water-cooled
condenser-receiver tank (option)
Содержание 098203
Страница 2: ......
Страница 3: ...MAGNUM TK 60275 4 MM Rev 3 08 15 Copyright 2012 Ingersoll Rand EMEIA Printed in Ireland...
Страница 193: ...Refrigeration Maintenance 191 Figure 163 Filter Drier...
Страница 200: ...Refrigeration Maintenance 198 Figure 169 Receiver Tank Figure 170 Water Cooled Condenser Tank...
Страница 257: ...255 Schematic Diagram RELEASED 19 Sep 2013...
Страница 258: ...256 Wiring Diagram Page 1 of 2 RELEASED 19 Sep 2013...
Страница 259: ...257 Wiring Diagram Page 2 of 2 RELEASED 19 Sep 2013...
Страница 263: ......