Diagnosis: Troubleshooting, Warnings and Alarm Codes
217
26
Evaporator Coil Temperature Too Low –
Check Evaporator Sensor
• When:
• During Chill or Frozen Mode: Evaporator
coil temperature is too low compared to
return air temperature under operating
conditions. The state will by time request
extended defrost, defrost or/and probe test.
• Indicates:
• Ice on the evaporator coil, need for defrost.
• Probe error.
• Using DATA menu inspect readings.
• Enter Manual Function Test menu and operate
evaporator fan at high speed to evaluate probe
spread.
27
System Low Pressure – Check Refrigerant
Charge
• When:
• The warning is related to the capacity
surveillance system which observes the
reefer machine capability to create a
temperature drop between return air and
supply air when expected to be running at
high capacity.
• Action:
• If the expected delta temperature is not
reached the warning are set and the
evaporator fans stopped to prevent heating
the cargo.
• Indicates:
• Lack of refrigerant.
• Check Refrigerant level.
• Check for refrigerant flow through the system,
look for restrictions.
28
Frozen Setpoint – Check Air Exchange
• When:
• If AVL door is open in frozen set point mode.
• Indicates:
• Air ventilation ought to be in position closed
when running within frozen mode.
• Check air ventilation door position.
Warnings and Controller Actions (Continued)
Warning
No.
Warning Message/Description
Controller Action/Corrective Action
Содержание 098203
Страница 2: ......
Страница 3: ...MAGNUM TK 60275 4 MM Rev 3 08 15 Copyright 2012 Ingersoll Rand EMEIA Printed in Ireland...
Страница 193: ...Refrigeration Maintenance 191 Figure 163 Filter Drier...
Страница 200: ...Refrigeration Maintenance 198 Figure 169 Receiver Tank Figure 170 Water Cooled Condenser Tank...
Страница 257: ...255 Schematic Diagram RELEASED 19 Sep 2013...
Страница 258: ...256 Wiring Diagram Page 1 of 2 RELEASED 19 Sep 2013...
Страница 259: ...257 Wiring Diagram Page 2 of 2 RELEASED 19 Sep 2013...
Страница 263: ......