202
Servicing The Unit
Taking Care of the Structure
Inspecting the Unit
Inspect the unit during unit pretrip inspection and every 1,000 operating hours for loose or broken wires
or hardware, compressor oil leaks, or other physical damage which can affect unit performance and
require repair or replacement of parts.
Checking the Mounting Bolts
Check and tighten all unit, compressor, and fan motor mounting bolts during pretrip inspections and every
1,000 operating hours. Unit mounting bolts should be tightened to a torque value of 204 N•m (150 ft-lb).
Compressor and fan motor mounting bolts should be tightened to a torque value of 20 to 21 N•m (15 to 20
ft-lb).
1.
Tighten Unit Mounting Bolts
2.
Tighten Compressor, Condenser Fan and
Evaporator Fan Mounting Bolts
Figure 173: Mounting Bolts
1
2
BEN074