ULTRA-CUT 200 XT
Manual 0-5304
APPENDIX
A-3
Line termination:
RS 485 and RS 422 are both “multi-drop protocols, that is there can be multiple devices on the same line. We do
not currently support more than one CCM. Until we do line termination should always be ON.
For RS 485 it is recommended that the communication lines be terminated at each end with the line’s characteristic
impedance. For RS 422 it is recommended the line be terminated at the receiver end.
The CCM has a line termination switch SW14 whose default position is ON. For CCMs that are not at the end of
the line (like CCM #1 & #2 below) switch off SW14.
RS 485 with multiple CCMs:
120
120
Signal GND also required but not shown.
SW14 OFF
SW14 OFF
SW14 ON
TSC 3000 (HMI)
or CNC using
2 wire RS 485
CCM #1
CCM #2
CCM # (last in line)
Data+
Data-
Art # A-09483
RS 422 4 wire half duplex:
Tx-
Tx+
Rx-
Rx+
Tx
Tx
Tx
Rx
Rx
Rx
Signal GND also required but not shown.
120
120
SW14 OFF
SW14 ON
CCM #1
CNC using
RS 422 half
duplex
SW14 OFF
CCM # (last in line)
CCM #2
Art # A-09484_AB
CCM Address:
When more than one device is used in parallel on a serial communication line each has to have a unique address.
The CCM has a switch SW10 to set the address of each CCM. The “0” factory setting is correct for system with one
plasma (one CCM). We do not currently support CCMs in parallel. When that becomes available details for set-
ting other addresses will be included in an updated manual explaining installation and set up of parallel systems.
Содержание ULTRA-CUT 200 XT
Страница 6: ...This Page Intentionally Blank...
Страница 15: ...ULTRA CUT 200 XT Manual 0 5304 SAFETY INSTRUCTIONS 1 5 This Page Intentionally Blank...
Страница 28: ...ULTRA CUT 200 XT SPECIFICATIONS Manual 0 5304 This Page Intentionally Blank...
Страница 76: ...ULTRA CUT 200 XT INSTALLATION Manual 0 5304 This Page Intentionally Blank...
Страница 142: ...ULTRA CUT 200 XT APPENDIX Manual 0 5304 APPENDIX 8 CCM CPU PCB Layout Test Point Test Point Art A 11675_AB...
Страница 144: ...ULTRA CUT 200 XT APPENDIX Manual 0 5304 APPENDIX 9 CCM I O PCB Layout Test Point Test Point Art A 11676_AC...
Страница 146: ...ULTRA CUT 200 XT APPENDIX Manual 0 5304 APPENDIX 10 Pilot PCB Layout Art A 11677 Test Point Test Point...
Страница 148: ...ULTRA CUT 200 XT APPENDIX Manual 0 5304 APPENDIX 11 Relay and Interface PCB Layout Test Point Test Point Art A 11678_AB...
Страница 150: ...ULTRA CUT 200 XT APPENDIX Manual 0 5304 APPENDIX 12 Display PCB Layout Test Point Test Point Art A 11679...
Страница 151: ...ULTRA CUT 200 XT Manual 0 5304 APPENDIX A 25 Display PCB Test Points TP1 GND TP2 5VDC TP3 24VDC...
Страница 152: ...ULTRA CUT 200 XT APPENDIX Manual 0 5304 APPENDIX 13 System Bias PCB Layout Test Point Test Point Art A 11680...
Страница 154: ...ULTRA CUT 200 XT APPENDIX Manual 0 5304 APPENDIX 14 Main Inverter Bottom PCB Layout Test Point Test Point Art A11681_AB...
Страница 156: ...ULTRA CUT 200 XT APPENDIX Manual 0 5304 APPENDIX 15 Main Inverter Top PCB Layout Test Point Test Point Art A11682_AB...
Страница 158: ...ULTRA CUT 200 XT APPENDIX Manual 0 5304 APPENDIX 16 Control and Fault PCB Layout Test Point Test Point Art A11683_AB...
Страница 160: ...ULTRA CUT 200 XT APPENDIX Manual 0 5304 APPENDIX 17 Cap Bias Bottom PCB Layout Art A 11685_AB...
Страница 161: ...ULTRA CUT 200 XT Manual 0 5304 APPENDIX A 35 APPENDIX 18 Cap Bias Top PCB Layout Art A 11686_AB...
Страница 162: ...ULTRA CUT 200 XT APPENDIX Manual 0 5304 APPENDIX 19 Suppressor PCB Layout Art A 11684_AB...
Страница 165: ...ULTRA CUT 200 XT Manual 0 5304 APPENDIX A 39 This Page Intentionally Blank...
Страница 227: ......