Typical applications
Optical presence detector thePixa P360 KNX
74
13.4.4
Important parameter settings
thePixa P360 KNX
DALI Gateway KNX plus
Standard or customer-defined parameter settings apply to unlisted parameters.
If desired, zone 1 can be adjusted to suit the specific application in thePixa Plug app.
Parameter page
Parameter
Setting
General
Installation height of detector
3 m (according to effective
installation height)
Zone definition
1 zone
Zone 1
General zone settings
Operating mode
master
Master operating mode
individual switching
Activate light
yes..
Light
Function light
constant lighting control..
Configuration type
fully automatic
Activate light standby time
yes..
Light / Time delays
Time delay after motion
1 min (as per customer specification)
Time delay after presence
10 min (as per customer
specification)
Duration standby
20 min (as per customer
specification)
Light / Control settings
Brightness setpoint value at
motion
100 lx (as per customer
specification)
Brightness setpoint value at
presence
500 lx (as per customer
specification)
Brightness setpoint value at
standby
50 lx (as per customer specification)
Parameter page
Parameter
Setting
Group 1
General information
Operating mode
Normal operation
Function of additional object
no Object
Enabled for panic mode
No
Behaviour
Switch-on value
100%
Switch-on behaviour
Dim to value in 10 s
Switch-off value
0%
Switch-off behaviour
Apply value immediately
Behaviour on value setting
Dim to value in 10 s
Time for dimming
10 seconds
Max. value for dimming
100%
Min. value for dimming
0%
Min/max values apply to
Dimming object
Switch-on via dimming
No