The application programme "thePixa P360 KNX"
Optical presence detector thePixa P360 KNX
48
Designation
Values
Description
Cyclical transmission HVAC
object
no
Value is not sent cyclically.
every minute
every 2 minutes
…
every 30 minutes
Value is sent cyclically with selected
time.
5.6.3.1
Time delays
Designation
Values
Description
Delay to motion
none
No switch-on delay when motion is
detected.
1 min…10 min…120 min
Time for the switch-on delay when
motion is detected to the motion
status.
Delay from motion to presence
none
When there is a change from motion
to presence in the detector (time not
adjustable), the status immediately
changes to presence.
1 min…30 min…120 min
When there is a change from motion
to presence in the detector (time not
adjustable), the status is only changed
to presence after the selected time.
Time delay after motion
none
No time delay for the motion status.
1 min…60 min…120 min
Time delay for the motion status.
Time delay after presence
none
No time delay after presence.
1 min…60 min…120 min
Time delay for the presence status.
Duration standby
none
No standby time for HVAC activated.
1 min…120 min
Time for the duration of the standby
status.