Typical applications
Optical presence detector thePixa P360 KNX
76
13.5.3
Important parameter settings
thePixa P360 KNX
DMG 2 T
Standard or customer-defined parameter settings apply to unlisted parameters.
If desired, zone 1 can be adjusted to suit the specific application in thePixa Plug app.
Parameter page
Parameter
Setting
General
Installation height of detector
3 m (according to effective
installation height)
Zone definition
1 zone
Zone 1
General zone settings
Operating mode
master
Master operating mode
individual switching
Activate light
yes..
Activate room occupancy
yes..
Light
Function light
constant lighting control..
Configuration type
fully automatic
Light / Time delays
Time delay after motion
1 min (as per customer specification)
Time delay after presence
10 min (as per customer
specification)
Light / Control settings
Brightness setpoint value at
motion
100 lx (as per customer
specification)
Brightness setpoint value at
presence
500 lx (as per customer
specification)
Room occupancy
Activate ventilation
yes..
Number of thresholds
3 thresholds
Delay time for threshold change
1 min (as per customer specification)
Number of persons for threshold 1 1 person (as per customer
specification)
Number of persons for threshold 2 3 persons (as per customer
specification)
Number of persons for threshold 3 5 persons (as per customer
specification)
Room occupancy / Ventilation
Output value for ventilation object
at greater or equal threshold 1
20% (as per customer specification)
Output value for ventilation object
at greater or equal threshold 2
60% (as per customer specification)
Output value for ventilation object
at greater or equal threshold 3
100% (as per customer
specification)
Parameter page
Parameter
Setting
General information
Type of basic module
DMG 2 T..
DMG 2 T channel C1: dimming
response
Load selection
automatic
DMG 2 T channel C2: dimming
response
Load selection
Fan (soft switching deactivated)