The application programme "thePixa P360 KNX"
Optical presence detector thePixa P360 KNX
37
Designation
Values
Description
Cycle time parallel switching
The parameter is visible if "parallel
switching" has been set at the
parameter <Master operating mode>.
5 s...25 s, 30 s…5 min
The interval between two telegrams
can be set to a maximum of 5 minutes.
Please keep in mind to always select
the interval between two trigger
telegrams to be shorter than the time
delay.
Cycle time aura effect
5 s...25 s, 30 s…5 min
The parameter is visible if "aura effect
(light)" has been set at the parameter
<Master operating mode>.
If the lighting is switched on in the
corresponding zone, the detector
cyclically sends a time value telegram.
Activate light
no
Light function is not used.
yes..
Light function is used.
Activates the parameter page Light.
Activate HVAC
no
HVAC function is not used.
yes..
HVAC function is used.
Activates the parameter page HVAC
Activate room occupancy
no
Room occupancy function is not used.
yes..
Room occupancy function is used.
Activates the parameter page Room
occupancy.
2
Only with
operating mode = Master
3
Only with
operating mode = Master
4
Only with
operating mode = Master