The application programme "thePixa P360 KNX"
Optical presence detector thePixa P360 KNX
24
5.3.2
Zone related objects
5.3.2.1
Objects for zone 1
5.3.2.1.1
Light
The following objects are available if "yes.." has been selected at <Activate light>.
Object 10: Z1 Light output – Switching
In "switching" mode, an ON telegram upon detection of motion and insufficient brightness, and an OFF telegram
upon the expiration of the time delay (motion/presence) or with sufficient brightness will be sent.
0 = absence or sufficient brightness (OFF)
1 = presence and insufficient brightness (ON)
In the "constant lighting control" function, at least objects 14 and 16 are used for constant lighting control if no
external button is involved. Both objects must be linked for a functioning constant lighting control. A different
response is produced depending on configuration.
Constant lighting control without motion/presence is also possible.
The response under manual control can be selected as either "school" or "office".
Object 11: Z1 Light input – Switching external button
1-bit input object for manual override of the detector using an external button.
Function: switching
Object 13: Z1 Light input – External button brighter/darker
4-bit input object for manual override of the detector using an external button.
Function: dimming
Object 14: Z1 Light output – Send value
Sends an 8-bit dimming telegram to control the dimming actuator.
Object available if "yes.." was additionally selected for <Lighting dimmable in switching mode>, or "constant
lighting control.." for <Function light>.
Object 15: Z1 Light input – Send value external button
1-byte input object for manual override of the detector using an external button.
Function: dimming
Object 16: Z1 Light input – Feedback value
Receives the current dimming value of the connected actuator via a 1-byte telegram.
Object available if "constant lighting control.." was selected at <Function light>.
Object 17: Z1 free switching – Switching
Free switch object, which sends the configured value to the bus, depending on the light switching status (0 or 1).