Parallel switching
Optical presence detector thePixa P360 KNX
57
7
Parallel switching
7.1
Master/Slave parallel switching
The operating mode (Master or Slave) is configured individually for each zone.
A zone with "Master in parallel switching" can be connected to several "Slave" zones. The zones can come from
their own detector, or from another detector.
For this purpose, the trigger outputs of the Slave zones are linked with the trigger input of the Master zone. The
Slaves only supply presence information from their detection area. The brightness measurement as well as the
management of all parameter settings are carried out at the master zone.
Example of a Master-Slave switching with 2 detectors:
7.2
Master/Master parallel switching
Several zones with "Master in parallel switching" can be linked with each other. Presence detection is completed
jointly, while light measurement, parameter settings and lighting control are individually processed by each master
zone. This results in several light outputs with their own light measurement but with joint presence detection.
Example of a Master-Master switching with 2 detectors: