Typical applications
Optical presence detector thePixa P360 KNX
83
13.7.4
Important parameter settings
thePixa P360 KNX (Master)
thePixa P360 KNX (Slaves)
RMG 4 U
Standard or customer-defined parameter settings apply to unlisted parameters.
If desired, the zones can be adjusted to suit the specific application in thePixa Plug app.
Parameter page
Parameter
Setting
General
Installation height of detector
3.0 m (according to effective
installation height)
Zone definition
1 zone
Zone 1
General zone settings
Operating mode
master
Master operating mode
parallel switching
Activate light
yes..
Light
Function light
switch light..
Configuration type
fully automatic
Brightness switching value
500 lx (as per customer
specification)
Light / Time delays
Time delay after motion
1 min (as per customer specification)
Time delay after presence
10 min (as per customer
specification)
Parameter page
Parameter
Setting
General
Installation height of detector
3.0 m (according to effective
installation height)
Zone definition
1 zone
Zone 1
General zone settings
Operating mode
slave
Parameter page
Parameter
Setting
RMG 4 U channel C1… C4:
configuration options
Function
Switching On/Off
Activation of function via
Switch object