2021-05-26
KNX manual
Optical presence detector thePixa P360 KNX
Страница 1: ...2021 05 26 KNX manual Optical presence detector thePixa P360 KNX ...
Страница 2: ...ers 36 6 Manual operation with push buttons 54 6 1 Manual operation via switching function without dimmable lighting 54 6 2 Manual operation via switching function with dimmable light 55 6 3 Manual operation with constant lighting control function 56 7 Parallel switching 57 7 1 Master Slave parallel switching 57 7 2 Master Master parallel switching 57 7 3 Telegram load when using parallel switchin...
Страница 3: ...l monitoring of room occupancy to control ventilation 1 zone 75 13 6 Constant lighting control additional manual override vis push button 4 zones 77 13 7 Master Slave parallel switching 81 13 8 Master Master parallel switching 84 13 9 Aura effect 86 13 10Adding the persons counted 91 ...
Страница 4: ...onstant at the brightness setpoint value The control is started fully automatically or manually via button Manual switching off and dimming influence or stop the control for the duration of the presence HVAC For each detection zone max 6 zones the presence information can be transmitted e g for heating ventilation or air conditioning control Each channel has a switch on delay and a time delay The ...
Страница 5: ...asurement Adjustment of brightness measurements via thePixa Plug app Configurable sensitivity of sensor Distinction between motion and presence Parallel switching of multiple presence detectors Master Slave or Master Master Test mode for checking function and detection area via app thePixa Plug Output of occupancy rate and occupancy density via telegram Integrated temperature sensor Ceiling instal...
Страница 6: ...ng value configurable in lux by using parameters Brightness switching value configurable in lux by using parameters and telegram Light time delay configurable by using parameters Aura effect for better orientation and greater safety Manual override by telegram 6 channels HVAC Z1 HVAC Z6 HVAC Configurable switch on delay and time delay Sending of operating mode Separate block telegram 6 channels ro...
Страница 7: ...ing range brightness switching value 5 3000 lx measurement off Setting range brightness setpoint 5 3000 lx light off Lighting time delay 0 s 60 min Standby dimming value light 1 25 of the dimming value Light standby time 0 s 60 min permanently on Switch on delay HVAC 0 s 120 min Time delay HVAC 0 s 120 min Runtime standby HVAC 0 s 120 min Standby value HVAC 0 255 Setting range temperature 15 60 C ...
Страница 8: ...Technical data Optical presence detector thePixa P360 KNX 8 Software Class A 2 1 Dimensions ...
Страница 9: ...nction between a radial frontal and tangential transverse walking direction The recommended installation height is 2 5 4 5 m The detection algorithm is designed for these installation heights The 6 zones can be positioned either in the ETS or via the thePixa Plug app In the app each zone can then be adjusted separately and individually Installation height Detection area walking Detection area sitt...
Страница 10: ...bel ETS database Label thePixa P360 KNX UP WH The designation TOP indicates the orientation of the detection area Also the area marked with TOP is displayed at the top of the screen on smartphone tablet During installation it is important to observe the orientation of the TOP symbol on the mounting frame picture on the right The sensor can only snap into one position on the mounting frame ...
Страница 11: ...2 2 1 Field of view For the detection of motion and presence to function correctly the field of view must be clear It has to be avoided for example that suspended lamps or partitions restrict the detection area Example of a lamp in the detector s field of vision ...
Страница 12: ... KNX IP Secure and secure communication via the TP and RF media using KNX Data Secure The following information refers to KNX Data Secure In the ETS catalogue KNX products supporting KNX Secure are clearly identified As soon as a KNX Secure device is included in the project the ETS requests a project password If no password is entered the device is included with Secure Mode deactivated However the...
Страница 13: ... the device is reset to the factory setting In this case all set safety related data will be deleted The ETS generates as many runtime keys as needed for the group communication you want to protect The ETS sends the runtime keys to the device to be configured via the bus Transmission takes place by encrypting and authenticating them via the tool key The runtime keys are never sent in plain text vi...
Страница 14: ...e zone occupancy per hour in Occupancy density zone utilisation per hour in Heat map Graphical display of the recorded motions over a defined period of time Export as csv file possible Parameter The following values are displayed or can be adjusted Actual temperature temperature calibration Actual brightness per zone brightness adjustment per zone Installation height Sensitivity of sensor Room def...
Страница 15: ...ne tablet to the presence detector The connection between thePixa P360 KNX and the app is established directly via Bluetooth Download the app thePixa Plug from the App Store or Google Play Store Open thePixa Plug and press in the menu bar Update Edit change password name Delete Search for new devices ...
Страница 16: ...ixa Plug app Optical presence detector thePixa P360 KNX 16 Device list of available thePixa devices appears Select device and confirm with OK A detailed description of the app can be found in our operating instructions ...
Страница 17: ... P360 KNX 5 1 Selection in the product database Manufacturer Theben AG Product family Physical sensors Product type Presence detector Program names thePixa P360 KNX The ETS database can be found on our website www theben de downloads Number of communication objects 170 Number of group addresses 255 Number of associations 255 ...
Страница 18: ...tes W C 9 004 21 Z1 Brightness setpoint value standby Receive lux value 2 bytes W C 9 004 22 Z1 Brightness value Send lux value 2 bytes R C T 9 004 24 Z1 Parallel switching Trigger output 1 bit C T 1 017 24 Z1 Aura effect Send motion status 2 bytes C T 7 005 25 Z1 Parallel switching Trigger input 1 bit W C 1 017 25 Z1 Aura effect Receive motion status 2 bytes W C 7 005 26 Z1 Aura effect Activate d...
Страница 19: ...Activate deactivate 1 bit W C 1 003 57 Z2 light standby function Activate deactivate 1 bit W C 1 003 58 Z2 light Block 0 1 bit W C 1 003 Block 1 1 bit W C 1 001 59 Z2 HVAC Switching 1 bit R C T 1 001 59 Z2 HVAC Send operating mode 1 byte R C T 20 102 59 Z2 HVAC Send value 1 byte R C T 5 010 60 Z2 HVAC Block 0 1 bit W C 1 003 Block 1 1 bit W C 1 001 61 Z2 number of persons Receive number 1 byte W C...
Страница 20: ...tch 3 Switching 1 bit R C T 1 001 96 Z3 Ventilation Send value 1 byte R C T 5 001 97 Z3 Room occupancy Block 0 1 bit W C 1 003 Block 1 1 bit W C 1 001 98 Z3 Occupancy rate Send value 1 byte R C T 5 001 99 Z3 Occupancy density Send value 2 bytes R C T 9 008 100 Z4 Light output Switching 1 bit R C T 1 001 101 Z4 Light input Switching external button 1 bit W C 1 001 103 Z4 Light input External button...
Страница 21: ... W C 5 001 136 Z5 Light input Feedback value 1 byte W C U 5 001 137 Z5 free switching Switching 1 bit R C T 1 001 138 Z5 Brightness setpoint value no motion presence Receive lux value 2 bytes W C 9 004 139 Z5 Brightness setpoint value motion Receive lux value 2 bytes W C 9 004 140 Z5 Brightness setpoint value presence Receive lux value 2 bytes W C 9 004 141 Z5 Brightness setpoint value standby Rec...
Страница 22: ...oint value standby Receive lux value 2 bytes W C 9 004 172 Z6 Brightness value Send lux value 2 bytes R C T 9 004 174 Z6 Parallel switching Trigger output 1 bit C T 1 017 174 Z6 Aura effect Send motion status 2 bytes C T 7 005 175 Z6 Parallel switching Trigger input 1 bit W C 1 017 175 Z6 Aura effect Receive motion status 2 bytes W C 7 005 176 Z6 Aura effect Activate deactivate 1 bit W C 1 003 177...
Страница 23: ...y after presence The response is as if the user switches it on via button The response depends on the selected control type See chapter 6 page 54 An OFF telegram switches the lighting channels Z1 Z6 according to the following conditions no motion when receiving the OFF telegram The light switches off immediately The running time delays for lighting channels Z1 Z6 and standby time are set to 0 Afte...
Страница 24: ... selected as either school or office Object 11 Z1 Light input Switching external button 1 bit input object for manual override of the detector using an external button Function switching Object 13 Z1 Light input External button brighter darker 4 bit input object for manual override of the detector using an external button Function dimming Object 14 Z1 Light output Send value Sends an 8 bit dimming...
Страница 25: ...ess setpoint value during operation Receives the lux value preset for the following case Presence is detected in zone 1 Constant lighting control uses the received value as a permanent new preset This will overwrite the parameter setting in the device Object available if constant lighting control was selected at Function light Object 21 Z1 Brightness setpoint value standby Receive lux value This e...
Страница 26: ...ting mode Master Slave parallel switching A Master zone receives the motion information from several Slaves zones in the room and switches or controls the lighting as required on the basis of the brightness measured by the Master The advantage is uniform switching with a defined brightness value For applications in corridors for example the Master is installed in the darkest position Master Master...
Страница 27: ...e it will be overridden by the aura effect After the aura effect has ended standby operation will be resumed Object available if aura effect light has been additionally selected at Master operating mode When using the Function light switching light it is imperative that yes is selected for Lighting dimmable in switching mode Object 26 Z1 Aura effect Activate deactivate Receive object Enables or di...
Страница 28: ...ivated Object available if switch command has been additionally selected at Type of telegram HVAC operating mode Sends a telegram with the operating status The telegrams can also be deactivated Object available if HVAC operating mode has been additionally selected at Type of telegram Value Sends a value telegram between 0 255 The telegrams can also be deactivated Object available if value has been...
Страница 29: ...mber of persons for thresholds 1 3 has been reached The telegrams can also be deactivated Object available if yes has been additionally selected at Activate switching Object 35 Z1 Threshold switch 3 Switching Sends an ON or OFF telegram when the configured number of persons for thresholds 1 3 has been reached The telegrams can also be deactivated Object available if yes has been additionally selec...
Страница 30: ...hePixa P360 KNX 30 Object 39 Z1 Occupancy density Send value Sends the average density of room occupancy within zone 1 during the last hour by means of a 16 bit telegram Example If on average half of the area was occupied the occupancy density is 50 See chapter 11 page 62 ...
Страница 31: ...in their function to the objects of zone 1 objects 10 to 39 5 3 2 4 Objects for zone 4 Objects 100 129 The objects 100 to 129 are for zone 4 and they are identical in their function to the objects of zone 1 objects 10 to 39 5 3 2 5 Objects for zone 5 Objects 130 159 The objects 130 to 159 are for zone 5 and they are identical in their function to the objects of zone 1 objects 10 to 39 5 3 2 6 Obje...
Страница 32: ...on presence and standby Switching Switching light and free switch object Dimming Dimming values for motion presence etc Control settings Parameters for constant lighting control HVAC General settings for heating control Time delays Time delays for motion presence and standby Room occupancy General settings for person counting and threshold configuration Ventilation Fan speed depending on room occu...
Страница 33: ...e monitored into several areas and to assign them to zones The zone allocation is displayed in the ETS as a sketch The selected zone definition is taken over by the detector and can be adjusted with the Bluetooth app if required Important With the predefined zone divisions zone 1 is always the entire detection area This must be taken into account for lighting control Device name optional text fiel...
Страница 34: ...ity password to allow the settings in safety mode to be changed via thePixa Plug app The security password must consist of 6 characters A Z 0 9 The security password can also be assigned later in thePixa Plug app Room definition standard meeting room Standard room e g office corridor etc The detector is installed in a meeting room Therefore the detection algorithm is adapted to these conditions Th...
Страница 35: ...temperature in the event of change The parameter is visible if yes has been set at the parameter Send temperature on bus no The measured temperature value is not transmitted depending on a change in temperature from 0 2 K from 0 5 K from 1 0 K from 1 5 K from 2 0 K from 4 5 K from 5 0 K The temperature value is sent if the measured value has changed by at least the configured value since the last ...
Страница 36: ... not connected to any actuator but only provides detection information to one or more zones in master operating mode Only applies to channels light and HVAC The channel room occupancy is not affected by this setting Master operating mode individual switching Zone operates autonomously parallel switching Depending on requirements additional zones are linked together as Master or Slaves for the exte...
Страница 37: ...s 25 s 30 s 5 min The parameter is visible if aura effect light has been set at the parameter Master operating mode If the lighting is switched on in the corresponding zone the detector cyclically sends a time value telegram Activate light2 no Light function is not used yes Light function is used Activates the parameter page Light Activate HVAC3 no HVAC function is not used yes HVAC function is us...
Страница 38: ...ut motion or presence detection For this purpose the parameter Brightness setpoint value no motion no presence is available Configuration type semi automatic fully automatic In semi automatic Configuration type switching on must always be carried out manually It is switched off automatically See chapter 6 page 54 In the fully automatic Configuration type the lighting channel automatically switches...
Страница 39: ... the selected time Send brightness value upon change no from 5 from 10 from 20 from 30 from 40 from 50 from 60 from 70 from 80 The parameter is visible if yes has been set at the parameter Send brightness value on bus The measured brightness value is not transmitted depending on a change in brightness The brightness value is sent if the measured value has changed by at least the configured value s...
Страница 40: ...ll be sent The lighting is not switched off if presence is detected with insufficient brightness Note If aura is detected at the time of unblocking or if standby on is activated and the brightness is fallen below the functions are executed 0 block 1 cancel block 0 cancel block 1 block block with ON telegram Activate light standby time no The light is switched off at the end of the time delay yes A...
Страница 41: ... switching value defines the minimum desired brightness The currently prevailing brightness is determined from the average of the entire zone If the brightness is below the switching value the light is switched on if motion or presence is detected Thanks to adaptive light measurement the turn off threshold is determined dynamically by the detector according to the ambient conditions Lighting dimma...
Страница 42: ...dby status or no motion no presence Time delay after presence none No time delay after presence 1 s 10 min 60 min Time to change from presence status to motion standby status or no motion no presence Duration standby The parameter is visible if yes has been set at the parameter Activate light standby time none No standby time for lighting activated 1 s 60 min The standby time causes dimming to the...
Страница 43: ...s Switch object light is sent cyclically with selected time Free switch object Switching value free switch object at No motion no presence send 0 send 1 do not send Switching status as a response to the detected motion status within the zone Motion send 0 send 1 do not send Presence send 0 send 1 do not send Standby9 send 0 send 1 do not send Block send 0 send 1 do not send Cyclical transmission f...
Страница 44: ...00 Dimming value as a response to the detected motion status within the zone Motion 0 50 100 Presence 0 100 Aura 1 10 25 Standby 1 10 25 Block 0 100 Cyclical transmission dimming object no Value is not sent cyclically every minute every 2 minutes every 30 minutes Value is sent cyclically with selected time 10 Parameters are visible if yes has been set at the parameter Lighting dimmable in switchin...
Страница 45: ...ted time Switch on dimming value 50 70 100 When the controller starts the lighting is switched on to the set Switch on dimming value and control starts from this value Lower control limit 1 10 25 Lowest permissible dimming value for control Upper control limit 50 100 Maximum permissible dimming value for control Switching off when there is enough brightness never switch off 5 min 10 min 9 h If the...
Страница 46: ...sponse with manual dimming school Manual dimming using a 4 bit object ends the control The manually set dimming value e g 75 applies until the end of presence office Manual dimming using a 4 bit object changes the brightness setpoint value for the control The new brightness setpoint value applies until the end of presence ...
Страница 47: ...e At type of telegram HVAC operating mode auto comfort standby temperature reduction at night frost protection do not send Send HVAC operating mode At type of telegram value 0 255 Any value between 0 and 255 can be sent Motion Type of telegram See above See above Presence Type of telegram See above See above Standby Type of telegram See above See above Block Type of telegram See above See above Bl...
Страница 48: ...atus Delay from motion to presence none When there is a change from motion to presence in the detector time not adjustable the status immediately changes to presence 1 min 30 min 120 min When there is a change from motion to presence in the detector time not adjustable the status is only changed to presence after the selected time Time delay after motion none No time delay for the motion status 1 ...
Страница 49: ...oom occupancy block with OFF telegram 0 block 1 cancel block block with ON telegram 0 cancel block 1 block Send number of persons to bus no yes The measured number of persons is not sent The measured number of persons is sent to the bus depending on the parameter Composition of the persons counted It is possible to add the number of persons from several zones Please observe the information in chap...
Страница 50: ...e number of persons has remained constant the number of persons will be transmitted again at the latest after expiration of the configured cycle time Activate ventilation no yes Opens the parameter page Ventilation Based on the set Threshold configuration predefined value telegrams are sent e g to control a fan Activate switching no yes Opens the parameter pages Threshold switch 1 3 Based on the s...
Страница 51: ... persons for threshold 3 5 6 5 Ventilation16 Designation Values Description Ventilation Output value for ventilation object at Below threshold 1 do not send No response 0 100 Selected value is sent when threshold 1 is fallen below Greater or equal threshold 1 do not send No response 0 20 100 Selected value is sent when threshold 1 Greater or equal threshold 2 do not send No response 0 40 100 Selec...
Страница 52: ... object 1 Output value for threshold switch object 1 at Below threshold 1 send 0 Send switch off command send 1 Send switch on command do not send No response Greater or equal threshold 1 send 0 Send switch off command send 1 Send switch on command do not send No response Greater or equal threshold 2 send 0 Send switch off command send 1 Send switch on command do not send No response Greater or eq...
Страница 53: ...ptical presence detector thePixa P360 KNX 53 Designation Values Description Cyclical transmission threshold switch object 1 no Value is not sent cyclically every minute every 2 minutes every 30 minutes Value is sent cyclically with selected time ...
Страница 54: ...ponse of lighting detector ON telegram The lighting is switched on with an ON telegram of the button The override is detected via object 11 and the lighting remains on for 30 minutes if the room is occupied Light measurement is deactivated The light measurement is reactivated after the 30 minutes In case of sufficient brightness an OFF telegram is sent to object 10 and the lighting switches off If...
Страница 55: ...oom is vacated before the 30 minutes have expired the light will be switched off normally after the completion of the set time delays Dimming telegram 4 bit The lighting is dimmed with a dimming telegram of the button The override is detected via object 13 and the new dimming value remains until the presence time delay has expired Afterwards the existing settings are applied again Value telegram 1...
Страница 56: ...ing response occurs school Constant lighting control is temporarily interrupted by manual dimming The brightness setpoint remains unchanged office After manual dimming to current brightness level constant lighting control remains temporarily active as new brightness setpoint After the time delays have expired the configured brightness setpoint will be restored Value telegram 1 byte The lighting is...
Страница 57: ...e Slaves only supply presence information from their detection area The brightness measurement as well as the management of all parameter settings are carried out at the master zone Example of a Master Slave switching with 2 detectors 7 2 Master Master parallel switching Several zones with Master in parallel switching can be linked with each other Presence detection is completed jointly while ligh...
Страница 58: ... Slave zone sends a telegram as long as a person is in the detection area The interval between two telegrams can be up to 5 minutes to reduce the telegram load on the bus Please note that the time delay can never be shorter than the interval between two telegrams in order to prevent unintentional switch off The parallel switching is compatible with all Theben KNX presence detectors ...
Страница 59: ... warehouse Each detector has zone 1 and zone 2 activated Trigger objects are available for sending and receiving the motion status Z1 aura effect send motion status Z1 aura effect receive motion status Z2 aura effect send motion status Z2 aura effect receive motion status They can be linked up to adjacent zones As soon as an aura signal is received and no motion was detected in the zone the lighti...
Страница 60: ...ing communication objects are available for each zone Zx number of persons Receive number Zx number of persons Send number In principle the number of persons is cascaded from detector to detector By linking inputs and outputs the result is the total number of persons An example for adding the persons counted with the necessary object links and parameter settings can be found in chapter 13 10 on pa...
Страница 61: ...for a zone In this example motion or presence was detected during 30 min Therefore the detector sends the percentage value of 50 with an 8 bit output object object 38 for zone 1 The value is transmitted every full hour The thePixa Plug app also displays the occupancy rate of the last 7 days graphically Example If several zones are active a separate chart is created for each zone ...
Страница 62: ...luation for a meeting room Total detection area 300 grids The occupancy density is evaluated in each meeting room The detectors send the ppm value with a 16 bit output object object 39 for zone 1 according to the respective utilisation This ppm value can be used for an individual visualisation This allows for example to determine which rooms are used to capacity and which are not Zone 1 includes 1...
Страница 63: ...d Calculation formula Ø number of persons or grids Occupancy time in min Number of grids in the zone 60 min 6 persons or grids 10 min 144 grids 60 min 4 persons or grids 20 min 144 grids 60 min 6 4 x x 1 000 000 Occupancy density in ppm x x 1 000 000 6 944 44 ppm x x 1 000 000 9 259 26 ppm 16 203 70 ppm ...
Страница 64: ...nce detector thePixa P360 KNX 64 The thePixa Plug app also displays the occupancy density of the last 7 days graphically Example If several zones are active a separate chart is created for each zone The displayed value in the app is ...
Страница 65: ...hePixa P360 KNX 65 12 Update Tool An ETS app is available for the KNX firmware update which can be downloaded free of charge For more detailed information on the procedure please refer to the following document https www theben de knx update ...
Страница 66: ...er defined parameter settings apply for the parameters not listed here 13 1 Presence and brightness dependent switching of light 1 zone The classic function of a presence detector is switching lights on only if a room is occupied and there is insufficient natural daylight The lighting is automatically switched off if the room is vacated or the amount of daylight increases 13 1 1 Devices thePixa P3...
Страница 67: ...xa Plug app Parameter page Parameter Setting General Installation height of detector 3 0 m according to effective installation height Zone definition 1 zone Zone 1 General zone settings Operating mode master Master operating mode individual switching Activate light yes Light Function light switch light Configuration type Fully automatic Brightness switching value 500 lx as per customer specificati...
Страница 68: ...emperature sensor measures the ambient temperature in order to regulate to the desired setpoint temperature 13 2 1 Devices thePixa P360 KNX 2269200 RMG 4 U 4930223 HME 6 T 4930245 13 2 2 Overview 13 2 3 Objects and links Links No thePixa P360 KNX No Mix combination Comment Object name function Object name function 10 Z1 Light output Switching 0 RMG 4 U channel C1 switch object Switching lighting o...
Страница 69: ...on Light Time delays Time delay after motion 1 min as per customer specification Time delay after presence 10 min as per customer specification HVAC Type of telegram HVAC operating mode Output value of HVAC object at as per customer specification HVAC Time delays Delay to motion 10 min as per customer specification Delay from motion to presence 30 min as per customer specification Time delay after...
Страница 70: ... presence detector detects presence in the corresponding zone The presence detector takes control only after the time delay has elapsed As an option the presence detector can be operated as a semi automatic device In this case the lighting must always be switched on manually The detector does not switch the lighting on automatically The presence detector switches off the lighting as usual if there...
Страница 71: ...witching 70 Z3 Light output Switching 10 RMG 4 U channel C2 switch object 71 Z3 Light input Switching external button 30 Button T2 1 switching 100 Z4 Light output Switching 20 RMG 4 U channel C3 switch object 101 Z4 Light input Switching external button 50 Button T3 1 switching 130 Z5 Light output Switching 30 RMG 4 U channel C4 switch object 131 Z5 Light input Switching external button 70 Button ...
Страница 72: ...s Operating mode master Master operating mode individual switching Activate light yes Light Function light Switch light Configuration type fully automatic Brightness switching value 500 lx as per customer specification Light Time delays Time delay after motion 1 min as per customer specification Time delay after presence 10 min as per customer specification Parameter page Parameter Setting Button ...
Страница 73: ...asing amount of daylight the artificial light automatically dims down and finally switches off The lighting is automatically dimmed to the standby dimming value if the room is vacated 13 4 1 Devices thePixa P360 KNX 2269200 DALI Gateway KNX plus 9070929 13 4 2 Overview 13 4 3 Objects and links Links No thePixa P360 KNX No DALI Gateway KNX plus Comment Object name function Object name 14 Z1 Light o...
Страница 74: ... delay after motion 1 min as per customer specification Time delay after presence 10 min as per customer specification Duration standby 20 min as per customer specification Light Control settings Brightness setpoint value at motion 100 lx as per customer specification Brightness setpoint value at presence 500 lx as per customer specification Brightness setpoint value at standby 50 lx as per custom...
Страница 75: ...led according to the number of persons With the 3 configurable thresholds the ventilation can be controlled according to the number of persons so the air always has the desired quality It is also possible to send the number of persons cyclically on the bus 13 5 1 Devices thePixa P360 KNX 2269200 DMG 2 T KNX 4930270 13 5 1 Overview 13 5 2 Objects and links Links No thePixa P360 KNX No DMG 2 T Comme...
Страница 76: ...alue at motion 100 lx as per customer specification Brightness setpoint value at presence 500 lx as per customer specification Room occupancy Activate ventilation yes Number of thresholds 3 thresholds Delay time for threshold change 1 min as per customer specification Number of persons for threshold 1 1 person as per customer specification Number of persons for threshold 2 3 persons as per custome...
Страница 77: ...g as the presence detector detects that the room is occupied The presence detector takes control only after the time delay has elapsed It is also possible to operate the presence detector as a semi automatic device This can be adjusted individually for each zone In this case the lighting must always be switched on by hand the detector does not switch on the lighting automatically For the zone defi...
Страница 78: ...ations Optical presence detector thePixa P360 KNX 78 13 6 2 Overview Obj 10 Obj 11 Obj 70 Obj 71 Obj 32 Obj 46 Obj 38 Obj 41 Obj 43 Obj 33 Obj 44 Obj 34 Obj 116 Obj 136 Obj 122 Obj 131 Obj 133 Obj 117 Obj 134 Obj 118 ...
Страница 79: ...ht input External button brighter darker 61 G2 dimming brighter darker 31 Button T2 brighter darker 74 Z3 Light output Send value 62 G2 set value value 76 Z3 Light input Feedback value 66 G2 status value 101 Z4 Light input Switching external button 88 G3 switching On Off 50 Button T3 switching 103 Z4 Light input External button brighter darker 89 G3 dimming brighter darker 51 Button T3 brighter da...
Страница 80: ...me delay after motion 1 min as per customer specification Time delay after presence 10 min as per customer specification Light Control settings Brightness setpoint value at motion 100 lx as per customer specification Brightness setpoint valu at presence 500 lx as per customer specification Parameter page Parameter Setting Group 1 4 General information Operating mode Normal operation Function of ad...
Страница 81: ...together One presence detector or zone is used as Master the others as Slaves The Slaves trigger the Master when motion is detected All settings as delay times and brightness thresholds are configured on the Master The trigger signal acts on the light and on the HVAC channel of the Master 13 7 1 Devices thePixa P360 KNX 2269200 RMG 4 U 4930223 13 7 2 Overview Master Slave Slave Obj 10 Obj 0 Obj 24...
Страница 82: ...aves 13 7 3 Objects and links Links No thePixa P360 KNX Master No RMG 4 U Comment Object name function Object name function 10 Z1 Light output Switching 0 RMG 4 U channel C1 switch object Switching lighting on and off No thePixa P360 KNX Master No thePixa P360 KNX Slaves Comment Object name function Object name function 25 Z1 Parallel switching Trigger input 24 Z1 Parallel switching Trigger output...
Страница 83: ...ngs Operating mode master Master operating mode parallel switching Activate light yes Light Function light switch light Configuration type fully automatic Brightness switching value 500 lx as per customer specification Light Time delays Time delay after motion 1 min as per customer specification Time delay after presence 10 min as per customer specification Parameter page Parameter Setting General...
Страница 84: ...esence among each other This extends the detection area It should be noted that each Master can only detect the light switched or controlled by itself Master Master parallel switching can be used independently of whether the Master is configured for switching or constant lighting control 13 8 1 Devices thePixa P360 KNX 2269200 RMG 4 U 4930223 13 8 2 Overview Instead of 2 different detectors a Mast...
Страница 85: ...ter RMG 4 U Standard or customer defined parameter settings apply to unlisted parameters If desired the zones can be adjusted to suit the specific application in thePixa Plug app Parameter page Parameter Setting General Installation height of detector 3 0 m according to effective installation height Zone definition 1 zone Zone 1 General zone settings Operating mode master Master operating mode par...
Страница 86: ...ress to the aura effect object Master A B and C On each Master connect the aura effect objects of the two zones with each other Example Connect object 54 with object 85 and object 55 with object 84 Connect the aura effect objects of the adjacent zones of the individual Master devices Example Connect Master A object 84 with Master B object 55 For the zone definition the template 4 zones per 1 4 of ...
Страница 87: ...Obj 44 Obj 34 Obj 46 Obj 38 Obj 74 Obj 62 Obj 76 Obj 66 Master A Obj 54 Obj 55 Obj 84 Obj 85 Obj 44 Obj 90 Obj 46 Obj 94 Obj 74 Obj 118 Obj 76 Obj 122 Master B Obj 54 Obj 55 Obj 84 Obj 85 Obj 44 Obj 146 Obj 46 Obj 150 Obj 74 Obj 174 Obj 76 Obj 178 Master C Obj 54 Obj 55 Obj 84 Obj 85 ...
Страница 88: ... KNX Master B No thePixa P360 KNX Master B Comment Object name function Object name 54 Z2 Aura effect Send motion status 85 Z3 Aura effect Receive motion status Object link Master B 55 Z2 Aura effect Receive motion status 84 Z3 Aura effect Send motion status Links No thePixa P360 KNX Master C No thePixa P360 KNX Master C Comment Object name function Object name 54 Z2 Aura effect Send motion status...
Страница 89: ...t name function Object name 84 Z3 Aura effect Send motion status 55 Z2 Aura effect Receive motion status Object link Master B Master C Links No thePixa P360 KNX Master C No thePixa P360 KNX Master B Comment Object name function Object name 54 Z2 Aura effect Send motion status 85 Z3 Aura effect Receive motion status Object link Master C Master B ...
Страница 90: ...utomatic Send aura at motion and presence Light Time delays Time delay after motion 1 min as per customer specification Time delay after presence 10 min as per customer specification Light Control settings Brightness setpoint value at motion 100 lx as per customer specification Brightness setpoint value at presence 500 lx as per customer specification Switch on dimming value at aura 10 Parameter p...
Страница 91: ...r counting persons due to the large area the total value can easily be determined by cascading With the information of the effective number of persons a red warning light can be controlled for example In addition the lighting of the entire meeting room is divided into 3 lighting groups switching 13 10 1 Devices thePixa P360 KNX 2269200 RMG 4 U 4930223 13 10 2 Overview Obj 32 Obj 31 Obj 31 Obj 32 O...
Страница 92: ...ber Cascading Nr thePixa P360 KNX Master A Nr RMG 4 U Comment Object name function Object name function 10 Z1 Light output Switching 0 RMG 4 U channel C1 switch object Switching lighting on and off Nr thePixa P360 KNX Master B Nr RMG 4 U Comment Object name function Object name function 10 Z1 Light output Switching 10 RMG 4 U channel C2 switch object Switching lighting on and off Nr thePixa P360 K...
Страница 93: ...switching Activate room occupancy yes Room occupancy Composition of the persons counted dynamic and static Send number of persons to bus yes Send number of persons upon change yes Parameter page Parameter Setting General Installation height of detector 3 0 m according to effective installation height Zone definition 1 zone Zone 1 General zone settings Operating mode master Master operating mode in...
Страница 94: ...uration type Fully automatic device Brightness switching value 500 lx as per customer specification Light Time delays Time delay after motion 1 min as per customer specification Time delay after presence 10 min as per customer specification Room occupancy Composition of the persons counted dynamic and static Activate switching yes Number of threshold 1 treshold Delay time for threshold change 1 mi...