6 Using the product
98
6.4.2.
Setting up base alarms
Any configuration changes are only transferred to the
probe/base once you have exited the
Alarm management
menu!
You should therefore exit the
Alarm management
menu
after editing.
1. Click on
Alarm management
in the navigation area.
- The data area shows the sub-menus
Base alarm settings
,
Component alarm settings, Channel alarm settings
.
2. Click on
Base alarm settings
.
- The
Base alarm settings
are shown in the display area.
Display
Explanation
Device alarm
Saveris Base
Setting options for the base alarms
Missing PC connection:
no response from
the PC
Memory almost full:
alarm when the base
memory overflows.
No GSM network:
alarm when there is no
GSM connection.
SMS overflow:
alarm when an error occurs
in SMS transmission.
Power failure:
alarm when the base power
supply fails.