PROBLEMS AND SOLUTIONS 

 

FAULT

 

CAUSE

 

SOLUTION

 

 

 

 

THE MACHINE WORKS 

NEITHER IN THE 

VENTILATION NOR IN THE 

HEATING MODE 

There's no electric voltage 

 

Check the electric connections. 

 

Check if line and auxiliary loads fuses are undamaged. 

 

Check  if  the  engine  thermal  protection  has  been 

activated. 

 

 

 

THE MACHINE DOES NOT 

WORK IN THE SUMMER 

VENTILATION MODE 

There's no electric supply to the 
fan engine 

 

Check the electric connections. 

 

Check if line and auxiliary loads fuses are undamaged. 

 

Check  if  the  engine  thermal  protection  has  been 

activated. 

 

 

 

THE MACHINE DOES NOT 

WORK IN THE HEATING 

MODE 

There's no electric supply to the 

gas or oil burner 

 

Check the electric connections. 

 

Check if line and auxiliary loads fuses are undamaged. 

 

Check if the room thermostat contact is closed. 

 

Check  if  the  engine  thermal  protection  has  been 

activated. 

 

Check if the safety thermostat has been activated. 

 

 

 

THE BURNER FLAME LIGHTS 

UP BUT AFTER A FEW 

SECONDS IT GOES OUT 

The electric connection has not 

been properly made 

 

Check the electric power poles (phase + n earth). 

Burner to be checked or out of 

order 

 

Check the burner calibration 

 

Replace the electric equipment of the device. 

 

Check and/or replace the flame detection electrode. 

 

 

 

THE FLAME OF THE OIL 

BURNER LIGHTS UP, BUT IT 

GOES OUT AFTER A FEW 

SECONDS 

The electric connection has not 
been properly made 

 

Check the electric power poles (phase + n earth). 

Burner to be checked or out of 
order 

 

Check the burner calibration. 

 

Replace the electric equipment of the device. 

 

Check and/or replace the burner photocells. 

 

 

 

THE BURNER GOES OFF 

ANOMOUSLY AND RANDOMLY 

The automatically restarting 
safety thermostat is operating 

 

Check if the flow directing fins are opened. 

 

Check that the air intake grills are not obstructed. 

 

Check the fan engine. 

Detachment of the burner flame 

 

Check the burner calibration. 

 

Check  that  the  machine  is  not  in  a  depressure 

environment. 

Wrongly installed room 

thermostat 

 

Check that the thermostat sensor is not in the machine 

warm air flow. 

 

 

 

ACTIVATION OF THE 

AUTOMATICALLY OR 

MANUALLY RESTARTING 

SAFETY THERMOSTAT 

Air circuit obstructed 

 

Check if the flow directing fins are opened. 

 

Check that the air intake grills are not obstructed. 

Warm air recirculation 

 

Check if the flow directing fins are opened, so that the 

warm air is not recirculated from the outlet to the inlet. 

 

Check the air intake temperature. 

Ventilation unit to be checked or 

out of order 

 

Check that the fan runner is cleaned. 

 

Check the efficiency of the fan engine 

 

Check the belt condition and the tension. 

 

Check  if  the  thermal  protection  of  the  fan  engine  has 

been anomalously activated. 

Excessive thermal strength 

 

Check the calibration of the gas or oil burner. 

 

 

 

ACTIVATION OF THE 

THERMAL PROTECTION OF 

THE FAN ENGINE 

Excessive  electric  absorption 

and/or heating of the fan engine 

 

Check that the air diffusion plenum is installed. 

 

Check the supply electric voltage. 

 

Check the air intake temperature. 

 

 

 

THE FAN DOES NOT START 

ONE MINUTE AFTER THE 

BURNER HAS BEEN 

SWITCHED ON 

Insufficient thermal power 

 

Check the calibration of the gas or oil burner. 

FAN-LIMIT double thermostat to 

be checked or out of order 

 

Check the calibration of FAN indexes. 

 

Replace the FAN-LIMIT double thermostat. 

 

 

 

THE FAN DOES NOT STOP 

WITHIN 4/5 MINUTES AFTER 

THE BURNER HAS GONE OFF 

Too high room temperature 

 

Check the air intake temperature. 

 

Check the machine exposition to solar irradiation. 

FAN-LIMIT double thermostat to 
be checked or out of order 

 

Check the calibration of FAN indexes. 

 

Check  if  the  white  button  has  been  set  on  the  AUT 

position. 

 

Replace the FAN-LIMIT double thermostat. 

 

 

 

Содержание ENERGY 105

Страница 1: ...TECHNICAL SPECIFICATIONS ASSEMBLY USE AND MAINTENANCE INSTRUCTIONS AIR CONDENSATION GENERATORS RANGE ENERGY...

Страница 2: ...ator mod ENERGY complies with Machinery directive 2006 42 EC Low Voltage Directive 2006 95 EC Regulation UE 2016 426 for Gas equipment Electromagnetic Compatibility Directive 2004 108 EC PIN NUMBER Th...

Страница 3: ...max thermal power 30 Combustion air 31 Operating principles with two stage burner 32 Operating principles with modulating burner 33 Electric connection 35 Wiring diagram reference 36 LIMIT and FAN saf...

Страница 4: ...used for a long time we suggest having the Technical Assistance Service or other skilled personnel put it back in service The machine shall be fitted only with original accessory equipment The Produc...

Страница 5: ...within the reach of children the packaging materials cardboard staples plastic bags etc as they may be potentially dangerous Do not install the unit near flammable material or in rooms with an aggres...

Страница 6: ...er with condensation of the combustion products which is discharged to the outside through a dedicated connection Combination with a burner with variable thermal power allows the continuous and linear...

Страница 7: ...he thermal energy accumulated by the heat exchanger can be exhausted by completely using it before the machine stops SAFETY function TR safety thermostat pre set calibration 80 C It is installed on th...

Страница 8: ...TIFICATION The warm air heaters can be identified through The Technical Plate applied on the machine specifying the main technical performance data ATTENTION In the event of damage or loss request a d...

Страница 9: ...smoke manifold 4 Rear smoke manifold 5 Inspection shutter of the heat exchanger 6 Smoke discharge pipe connector 7 Burner nozzle 8 Flame eyehole 9 Ventilation unit 10 Ventilation unit engine 11 Conden...

Страница 10: ...Front smoke manifold 5 Flame eyehole 6 Gas or fuel burner 7 Combustion chamber Combustion products perform an inversion in the combustion chamber are routed to the first exhaust manifold front manifol...

Страница 11: ...15 5 825 755 450 4 1 50 0 1 00 0 2 12 0 1 50 0 1 44 0 1 00 0 940 1 42 5 1 35 5 825 755 535 5 1 70 0 1 20 0 2 35 0 1 70 0 1 64 0 1 20 0 1 14 0 1 62 5 1 55 5 825 755 750 6 2 09 0 1 27 0 2 87 0 2 09 0 2...

Страница 12: ...10 0 Net fume temperature 2 C 205 210 185 205 184 154 182 210 Fume mass flow rate Kg h 93 181 277 334 559 792 1 130 1 563 Air temperature gradient K 34 38 43 38 45 44 45 37 Consumption 3 G20 methane...

Страница 13: ...low rate m h 4 600 8 000 11 000 15 000 21 500 31 000 43 000 71 000 Standard static pressure Pa 450 450 450 450 450 450 450 450 Fan Quantity No 1 1 1 2 1 2 3 3 Size Mod AT 12 9 S AT 15 15 S AT 18 13 S...

Страница 14: ...8 6 970 910 P min kW 119 1 166 196 6 196 6 154 6 188 300 234 3 Useful efficiency 1 nom 82 2 85 7 83 3 86 8 81 6 85 1 80 1 83 5 pl 90 5 92 7 90 93 9 92 9 95 3 89 5 94 7 Electrical energy consumption el...

Страница 15: ...6 8 81 6 85 1 80 1 83 5 pl 90 5 90 1 91 4 93 0 95 3 89 5 94 8 Electrical energy consumption el max kW 0 6 0 75 1 8 2 1 8 2 8 2 2 el min kW 0 6 0 75 1 8 2 1 8 2 8 2 2 el sb kW 0 03 0 03 0 05 0 05 0 05...

Страница 16: ...ES The unit is certified in EU countries and in the countries that will soon enter the EU according to the gas categories shown below COUNTRY CATEGORY AL II2H3B P II2H3P AT II2H3B P BE I2E R B I3P BG...

Страница 17: ...t of 30 kW the thermal efficiency referring to the lower calorific value Hi of the fumes is 95 5 while the total efficiency referring to the lower calorific value Hi including the energy recovery of l...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...20...

Страница 21: ...liance During transportation and handling it is forbidden to stand near the unit It is advisable to use personal safety equipment In order to prevent rainwater from entering the appliance the plastic...

Страница 22: ...flue chimney be easily connected to the fuel tank or to the gas grid be close to an electrical socket allow for all maintenance operations and inspections to be carried out easily be fitted with the v...

Страница 23: ...ormal control and or maintenance operations and not to create obstacles to the flow of air WARNING Any restrictions deriving from specific Laws and regulations must also be observed for example regard...

Страница 24: ...ctor and diagram of the connection to the flue 1 Condensate drainage connector 2 T connector 3 Flue TYPE A mm B mm E external mm 1 1 300 270 150 2 1 655 380 200 3 1 905 450 250 4 1 905 500 250 5 2 135...

Страница 25: ...or flue gas pipes might amplify the burning noise and affect negatively the combustion parameters Joint seals should be made of materials resistant to the thermal and chemical stress caused by the com...

Страница 26: ...n pipes should be connected independently avoiding their convoy fumes must not come out of the condensate drain For this reason it is mandatory to install a siphon equipped with a float if any condens...

Страница 27: ...ensate drain system must not weigh on the equipment and must be suitably and separately mounted The configuration of the condensate discharge system must allow for the easy removal of the various insp...

Страница 28: ...ircuit to the upper outlet flange of the machine WARNING The connection with ducting and or accessories shall be carried out by fitting suitable sealing gaskets This precaution is necessary to assure...

Страница 29: ...with the burner and supply ramp manuals provided together with the devices BURNER COMBINATIONS The warm air heater and the burner should be connected only by skilled and authorized personnel taking i...

Страница 30: ...e performance point of view TYPE 1 2 3 4 5 6 7 8 Thermal power kW 68 2 115 1 175 7 246 1 354 8 502 9 715 2 1089 8 RG2KD 41 5 94 5 BG7 1D 77 149 5 RL 22 BLU 89 261 RL 32 BLU 166 356 RL 42 BLU 191 598 R...

Страница 31: ...of new burner models is in continuous evolution For specific needs consult the Manufacturer ATTENTION If the unit operates on gas the EC certification is valid only if it is combined with the burner...

Страница 32: ...ame has been ignited also the ventilation unit starts thus releasing warm air in the room When the room thermostat detects that the first set temperature level has been reached it switches the burner...

Страница 33: ...s If the ambient thermostat detects that the temperature set has been reached it gives the consent to switch off the burner After approx 3 4 min when the heat exchanger has completely cooled the venti...

Страница 34: ...needs The burner will operate at maximum heat output when the temperature is very low with respect to the value set and then progressively decreases if the temperature increases If the ambient chronot...

Страница 35: ...system are suitable for the maximum power absorbed by the unit indicated on the information plate Respect polarity in the connection of the power supply phase neutral In any case you should check tha...

Страница 36: ...d below TYPE HEAD DIAGRAM CODE DIAGRAM standard high 1 10014128 TC 2 3 4 10017649 TC 5 10014128 TC 10017648 TC 6 10017649 TC 7 10017648 TC 8 10017847 TC 10017848 TC In case of doubts do not perform an...

Страница 37: ...sensor is placed on the warm air outlet FAN FUNCTION calibration 25 35 C It activates the fan max 60 seconds after the burner has started and it stops it approx 4 minutes after it has stopped Thus it...

Страница 38: ...matically restored after removing the causes that have triggered it It shall be correctly calibrated when it is used for the first time ELECTRIC CONNECTION AND CALIBRATION PROCEDURE When the warm air...

Страница 39: ...s of portability are supplied in separate sections Therefore the thermostats are electrically connected to the electric panel but they should be placed in the relevant position during the installation...

Страница 40: ...ing temperature of the TR thermostat should be set to 55 C FAN START TIMER The electric panel of some models those having a starting fan engine includes a timer whose function is to start the ventilat...

Страница 41: ...rm conveyor If there is a three phase electric motor to change the direction of rotation simply invert a phase of the supply line without tampering with the wiring of the electrical panel It is also n...

Страница 42: ...l the belt 5 and stretch it In the case of models equipped with more than one motor each motor must be adjusted and its electrical absorption must be checked independently New belts after a certain pe...

Страница 43: ...correctly calibrated Make sure that the safety thermostats LM and TR do not intervene when not necessary Check that no faults have been reported on the safety devices present on the machine Make sure...

Страница 44: ...f the FAN LIMIT safety temperature it restores the burner operations after they have been blocked because of overheating RESTORE BUTTON OF THE FAN ENGINE THERMAL PROTECTION Placed inside the electric...

Страница 45: ...to the wire absorption This electrical power value should be multiplied per 1 73 and it should be compared to the data written on the engine plate If a machine has more than one engine each engine sho...

Страница 46: ...ls are also hermetic and prevaricated In the 6 and 7 type models the bearings are monobloc support which generally do not require lubrication and on which the connection for the lubricator is provided...

Страница 47: ...he connector 5 in models 3 8 type only remove the side panels 7 and the inspection doors 6 Remove the reticular turbulators 10 using the extraction hook12supplied clean the pipe bundle elements 3 with...

Страница 48: ...the combustions products is not provided together with the machine CUSTOMER SERVICE The installation commissioning and maintenance of the warm air heater shall be performed by qualified technical pers...

Страница 49: ...pened Check that the air intake grills are not obstructed Check the fan engine Detachment of the burner flame Check the burner calibration Check that the machine is not in a depressure environment Wro...

Страница 50: ...eck the calibration of the gas or oil burner THERE ARE GAPS IN ITS FUNCTIONING Warm air recirculation Check if the flow directing fins are opened so that the warm air is not recirculated from the outl...

Страница 51: ...51 NOTES...

Страница 52: ...0461 51 24 32 www tecnoclimaspa com tecnoclima tecnoclimaspa com Since the Company is constantly involved in the continuous improvement of all its production the aesthetic and dimensional features te...

Отзывы: