FIXED PROTECTIONS
In order to avoid the accidental contact with the movable parts of the machine, check if the following fixed
protections have been properly installed:
•
Inlet grill/s
•
Side cover panel/s
•
burner case
ACCESSORIES
To install the accessories, follow the instructions included in the relevant package.
BURNER ASSEMBLY AND SETTING
(Gas or fuel) burners and the supply ramp (for gas burners) are delivered dismantled and in different parcels,
on request.
The installer is in charge of mounting, electrically connecting and setting the burner. These operations should
be carried out only by qualified and skilled personnel, carefully complying with the burner and supply ramp
manuals (provided together with the devices).
BURNER COMBINATIONS
The warm air heater and the burner should be connected only by skilled and authorized personnel, taking into
account the specifications of this manual and the instructions of the burner:
Dimensions of the burner nozzle:
Table: dimensions of the nozzle housing the burner:
TYPE
1
2
3
4
5
6
7
8
mm
130
165
165
215
215
300
300
295
B
mm
75
90
160
210
210
240
250
180
To select the dimension of the burning head (diameter and length), refer to the table above. If
the head is too short, it might cause the front wall of the combustion chamber to overheat; if the
head is too long, it might cause the back wall of the combustion chamber to overheat.
For operation with a diesel burner, to avoid frequent cleaning, it is advisable to remove the reticular turbulators.