- 44 -
CONTROLS
HEATING / STOP / VENTILATION SWITCH:
It is placed in the machine electric panel and it is used to select the operating cycle:
•
Set the machine on the "heating" symbol, it pre-sets the machine so that the fan and burner will
automatically start when heated is requested.
•
Set the machine on the "heating" symbol, it pre-sets the machine so that the burner will not operate.
•
Set the machine on the "heating" symbol, it stops the warm air heater. The burner works for a certain
period in order to exhaust the heat accumulated in the heat exchanger.
ROOM THERMOSTAT:
It should be installed inside the room to be heated at approx. 1,5 meters above the ground and sheltered
from hot or cold air currents. It starts or switches off the machine according to the temperature set and to the
temperature detected.
BURNER RESTORE BUTTON:
Placed on the burner itself, it restores the burner operations after they have been blocked.
LIMIT THERMOSTAT RESTORE BUTTON:
Red, placed on the body of the FAN
–
LIMIT safety temperature, it restores the burner operations, after they
have been blocked because of overheating.
RESTORE BUTTON OF THE FAN ENGINE THERMAL PROTECTION:
Placed inside the electric panel, on the thermal relays block, it restores the operation of the ventilation unit,
after they have been blocked because of improper functioning or excessive electric absorption of the fan
engine.
ATTENTION!!!
Before restoring any device, the problem that has triggered the safety protection should
be detected and solved. In case of doubt, please contact the closest Authorized
Assistance Centre, which will provide you with the necessary technical assistance.
INDICATORS
VOLTAGE INDICATOR
Placed on the electric panel, it is a green light indicator, which turns on when there is electric voltage.
BURNER BLOCK INDICATOR:
Placed on the burner itself, it a red light indicator, which turns on when the burner is blocked. The indicator is
also the restore button.
SAFETY STOP INDICATOR:
Placed on the machine electric panel, it is a red light indicator, which turns on in the following cases:
•
LIMIT safety thermostat activation.
•
activation of the thermal protection of the fan engine.