- 31 -
Table combination with Riello MODULATING GAS burners (from the performance point of view):
TYPE
1
2
3
4
5
6
7
8
Thermal power
(kW
)
68
,2
11
5,1
17
5,7
24
6,1
35
4,8
50
2,9
71
5,2
10
89
,8
BS 2/M
26-91
BS 3/M
48-195
BS 4/M
68-250
RS 25/M BLU
44-370
RS 34/M MZ
45-390
RS 45/M BLU
90-550
RS 44/M MZ
80-550
RS 68/M BLU
150-860
RS 120/M BLU
300-1300
Always check that the combustion head dimensions are compatible with the burner nozzle.
To connect it to the gas supply ramp, consult the burner technical sheets and select the fittest
model on the basis of the thermal power and of the fuel pressure available in the network. The
mentioned documents also specify the relevant fittings, if any.
The availability of new burner models is in continuous evolution. For specific needs, consult the Manufacturer.
ATTENTION
If the unit operates on gas, the EC certification is valid only if it is combined with the burner
indicated in the table. For different combinations, consult the Manufacturer.
The minimal gas supply pressure should be such as to offset the friction losses of the supply ramp
increased by an approx. 30% safety coefficient.
The gas supply pressure should always be stable and never exceed the max. value specified in
the instructions of the burner.
COMBUSTION AIR
The warm air heater should be installed in compliance with the Regulations in force and it should be used only
in an adequately ventilated room.
Check that the combustion air inlet is always free from any obstacles (leaves, sheets of paper, nylon pieces,
etc.).
Proper air openings should be made, in compliance with the relevant Regulations.