Technical data
Proline Promass F 500 EtherNet/IP
258
Current output 0/4 to 20 mA
4 to 20 mA
Failure mode
Choose from:
• 4 to 20 mA in accordance with NAMUR recommendation NE 43
• 4 to 20 mA in accordance with US
• Min. value: 3.59 mA
• Max. value: 22.5 mA
• Freely definable value between: 3.59 to 22.5 mA
• Actual value
• Last valid value
0 to 20 mA
Failure mode
Choose from:
• Maximum alarm: 22 mA
• Freely definable value between: 0 to 20.5 mA
Pulse/frequency/switch output
Pulse output
Failure mode
Choose from:
• Actual value
• No pulses
Frequency output
Failure mode
Choose from:
• Actual value
• 0 Hz
• Defined value (f
max
2 to 12
500 Hz)
Switch output
Failure mode
Choose from:
• Current status
• Open
• Closed
Relay output
Failure mode
Choose from:
• Current status
• Open
• Closed
Local display
Plain text display
With information on cause and remedial measures
Backlight
Red backlighting indicates a device error.
Status signal as per NAMUR recommendation NE 107