Electrical connection
Proline Promass F 500 EtherNet/IP
68
Status input
1
2
3
A0028764
24
Connection example for status input
1
Automation system with status output (e.g. PLC)
2
Power supply
3
Transmitter: Observe input values
7.6
Hardware settings
7.6.1
Setting the device address
The IP address of the measuring device can be configured for the network via DIP switches.
Addressing data
IP address and configuration options
1st octet
2nd octet
3rd octet
4th octet
192.
168.
1.
XXX
↓
↓
Can only be configured via software addressing
Can be configured via software addressing
and hardware addressing
IP address range
1 to 254 (4th octet)
IP address broadcast
255
Addressing mode ex
works
Software addressing; all DIP switches for hardware addressing are set to OFF.
IP address ex works
DHCP server active
Software addressing: The IP address is entered via the
IP address
parameter
Setting the IP address: Proline 500 - digital
Risk of electric shock when opening the transmitter housing.
‣
Before opening the transmitter housing:
‣
Disconnect the device from the power supply.
The default IP address may
not
be activated → 70.