Proline Promass F 500 EtherNet/IP
Technical data
255
16.4 Output
Output signal
EtherNet/IP
Standards
In accordance with IEEE 802.3
Current output 0/4 to 20 mA
Current output
0/4 to 20 mA
Maximum output values
22.5 mA
Current span
Can be set to:
• 4 to 20 mA (active)
• 0/4 to 20 mA (passive)
Ex-i, passive
Open-circuit voltage
DC 28.8 V (active)
Maximum input voltage
DC 30 V (passive)
Load
0 to 700 Ω
Resolution
0.38 µA
Damping
Adjustable: 0.07 to 999 s
Assignable measured
variables
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Electronic temperature
• Oscillation frequency 0
• Oscillation damping 0
• Signal asymmetry
• Exciter current 0
The range of options increases if the measuring device has one or more
application packages.
Pulse/frequency/switch output
Function
Can be set to pulse, frequency or switch output
Version
Open collector
Can be set to:
• Active
• Passive
Ex-i, passive
Maximum input values
DC 30 V, 250 mA (passive)
Open-circuit voltage
DC 28.8 V (active)
Voltage drop
For 22.5 mA: ≤ DC 2 V
Pulse output
Maximum input values
DC 30 V, 250 mA (passive)