Electrical connection
Proline Promass F 500 EtherNet/IP
70
2. Depending on the housing version, unscrew or open the housing cover and
disconnect the local display from the main electronics module where necessary.
3. Set the desired IP address using the corresponding DIP switches on the I/O
electronics module.
4. Reverse the removal procedure to reassemble the transmitter.
5. Reconnect the device to the power supply.
The configured device address is used once the device is restarted.
7.6.2
Activating the default IP address
The DHCP function is enabled in the device at the factory, i.e. the device expects an IP
address to be assigned by the network. This function can be disabled and the device can be
set to the default IP address 192.168.1.212 by DIP switch.
Activating the default IP address by DIP switch: Proline 500 - digital
Risk of electric shock when opening the transmitter housing.
‣
Before opening the transmitter housing:
‣
Disconnect the device from the power supply.
Power
I/O 2
I/O 3
I/O 3
Off
On
1
4
3
2
4.
3.
-
+
-
ESC
2.
Power
open
press
open
press
ESC
E
+
-
I/O 4
Power
I/O 2
I/O 3
1.
A0034500
1. Loosen the 4 fixing screws on the housing cover.
2. Open the housing cover.
3. Fold open the terminal cover.
4. Set DIP switch No. 2 on the I/O electronics module from
OFF
→
ON
.
5. Reverse the removal procedure to reassemble the transmitter.
6. Reconnect the device to the power supply.
The default IP address is used once the device is restarted.