26
KAS06 Cas. flow rate measure-
ment
Type of flow measurement on : local, each station of the cascade has its own flow
meter
off : central, the flow in the cascade is measured cen-
trally by the master
on/off
-
25
36:023
KAS07 Central cas. circ. pump
Central circulation pump
Adjuster for whether there is a circulation pump at
each station in the cascade or one circulation pump for
the entire cascade.
0: Decentralized circulation pump, each station has its
own circulation pump, settings and functions are local.
1: Central circulation pump, the circulation mode ther-
mal disinfection is set on the station which is also con-
nected to the pump. All functions are then executed
centrally for the cascade.
Note:
The tapping support must be set on each station
where this is to be used.
0 ... 1
-
25
36:031
The visible values vary depending on the selected hydraulic variant, as well as option, and depend on the input password, "Key" column.