29
Maximum circulation temperature
As soon as the value
ZIR02 TMAX CIRCULATION
is exceeded at the TBZ sensor, tapping
support stops.
Circulation pump run-times
To avoid unnecessary cycling of the circulation pump WWC, a minimum run-time
ZIR11
CIRC. PULSE RUN-TIME
and a minimum off-time
ZIR12 CIRC. PULSE OFF-TIME
are ac-
tivated.
8.4
Calibrating circulation volumes
Functions
Calibrating circulation volumes
The value
ZIR07 CIRCULATION FLOW RATE
can be determined using an automatic cal-
ibration process
ZIR06 CIRC.CALIBRATION
.
The following selection is available:
0: Off. No calibration.
1: Manual calibration; reset value to "0" after calibration has been done.
2: Automatic calibration - every Monday at 02:00 a.m.
Calibration status
If calibration is active, then its status can be tracked under
ZIR09 CIRC. CALIBRATION
STATUS
.
0: Inactive. - Calibration not yet done or last calibration obsolete.
1..8: Measurements 1..8. - If measurements 1..4 OK, transition to 9; otherwise, carry out
measurements 5..8 and then evaluate.
9: Calibration successful
10: Start
11: Error - Flow despite pump being switched off.
12: Error - Flow rate fluctuation too great with the pump switched on.
Calibration
To calibrate
ZIR07 CIRCULATION FLOW RATE
, a maximum of 2 measuring
blocks with 4 measurements each are carried out. If the measured values do not deviate
by more than the defined tolerance
ZIR05 CIRC. CALIB. TOLERANCE
, calibration was
successful and the value is displayed under
ZIR07 CIRCULATION FLOW RATE
.
8.5
Thermal disinfection
Functions
Thermal disinfection
Can be used if
ZIR00 CIRCULATION MODE
is not equal to 0. The following selection is possible:
0: No function
15: With pump WWC and TBZ
16: With pump WWC and TKW
17: With pump WWC and TWW
18: With pump WWC and TBZ; TKW; TWW
If the enable is given through the time program
LEG05 THM.DISINF. TIME PROGRAM
,
thermal disinfection is carried out.
The DHW is heated to the nominal temperature value
LEG01 THERM.DISINFECT. TEMP.
and held at the selected sensor for
LEG02 TEMP. HOLDING TIME
. The circulation pump
is active during the protection function.
In order to reach the required temperature on the reference sensor, the set point is boosted
on TWW. The value of the charging boost
LEG03 TSET HYSTERESIS, THM.DIS
is ad-
justable.