13
6.6
BAS05 Recharging, primary
Options
Option - (Re-)charging the storage tank.
If the temperature at the top storage tank
sensor TO1 is less than the current set point
T1Oset, recharging is enabled or heat is
requested.
If the current set point is exceeded at the top
storage tank sensor TO1, recharging is disa-
bled or the heat request is ended. Recharg-
ing can be additionally restricted via a time
program.
Sensor side
TO1 sens. Tank, top
B7
V2
+
-
Voltage 5 V DC
Ground
GND
TWW sensor B6
Flow, sec. V1
- GND
- S2
Ground GND
PWM/ 0 ... 10 V S1
Ground GND
eBUS e
Mains side
TKW sensor B5
N
Ground GND
5
WWL recharging, primary
TPV sensor B4
4
- GND
3
- B3
2 -
- GND
1 PP primary pump
- B2
L’ Support phase
- GND
L Phase 230 V
- B1