Pulse

Activates the circulation pump via a short tapping operation or switch with pulse control.

 

Flow [V] > 0, then WWC active for time period 

ZIR11 CIRC. PULSE RUN-TIME

, afterwards 

WWC disabled for time period 

ZIR12 CIRC. PULSE OFF-TIME

The running and blocking times must be adapted to the volume in the pipe net, but should 
be longer as 1 minute.

Protection - Maximum circulation 
temperature

As soon as the value 

ZIR02 TMAX CIRCULATION

 is exceeded at the TBZ sensor, the 

WWC circulation pump stops.

Circulation modus with consumption

Optionally, the circulation pump can be controlled with an active water consumption by the 
active circulation mode or the water consumption support.
Whether the circulation mode is active with a consumption may be set by 

ZIR13 Circ mode 

with consumption

.

0: on Circulation modus is always active with consumption
1: off Circulation modus is always inactive with consumption

8.3

Tapping support

Functions

Tapping support

When the option 

BAS05 CIRCULATION MODE

 is active, the "Tapping support" function 

can be used to improve the control quality of the fresh water station.
For this, a minimum flow (switch-on threshold) 

ZIR08 MIN.FL TAPPING SUPP.

, a maxi-

mum flow (switch-off threshold) 

ZIR09 MAX.FL TAPPING SUPP.

 and a circulation volume 

ZIR07 CIRCULATION FLOW RATE

 are defined.

 

If tapping is active and V is greater than 

STE15 MIN. TAPPING RATE

, but less than 

ZIR08 

MIN.FL TAPPING SUPP.

, circulation pump WWC is activated to increase the flow rate.

If the tapping volume increases and exceeds the switch-off threshold 

ZIR09 MAX.FL TAP-

PING SUPP.

, circulation pump WWC is stopped.

Function

STE15 MIN. TAPPING RATE

 < 

SEK04 DHW FLOW RATE

 < 

ZIR08 MIN.FL TAPPING 

SUPP.

, then WWC active

ZIR09 MAX.FL TAPPING SUPP.

 < 

SEK04 DHW FLOW RATE

, then WWC off.

Minimum flow for

 

tapping support

This value can be set in l/ min under 

ZIR08 MIN.FL TAPPING SUPP.

Maximum flow for

 

tapping support

The maximum flow rate 

ZIR09 MAX.FL TAPPING SUPP.

 is calculated from the circulation 

volume 

ZIR07 CIRCULATION FLOW RATE

 plus the minimum flow rate 

 

ZIR08 MIN.FL TAPPING SUPP.

 in l/ min.

Circulation volume

The circulation volume 

ZIR07 CIRCULATION FLOW RATE

 is the throughput when circu-

lation pump is active with no tapping.

 

The value 

ZIR07 CIRCULATION FLOW RATE

 can be entered in l/ min or be determined 

by means of calibration 

ZIR06 CIRC.CALIBRATION

; see "8.4 Calibrating circulation vol-

umes", page 29.

8.3.1 Protective function

Flow rate fluctuation

If the flow rate moves in the range of the maximum flow (switch-off threshold) 

 

ZIR09 MAX.FL TAPPING SUPP.

 minus the tolerance 

ZIR05 CIRC. CALIB. TOLER-

ANCE

, a 3-min. timer starts; after it expires, the circulation pump WWC is stopped to de-

termine the current flow.

Содержание TACOTHERM FRESH PETA ES 5941S

Страница 1: ...ova Group AG Neunbrunnenstrasse 40 CH 8050 Zurich T 41 44 735 55 55 F 41 44 735 55 02 group taconova com 03 2017 Art Nr 212788 EA Nr 1243 en CONTROLLER MANUAL TACOTHERM FRESH PETA FRESH HOT WATER STAT...

Страница 2: ...mode 14 7 2 INFO parameter overview 15 7 3 Querying temperatures and operating data 16 7 4 Values on information level 17 7 5 Parameters MENU overview 19 7 6 Enter password 20 7 7 Clock program 21 7...

Страница 3: ...underground Never run device above or below limit values as listed under the technical data When it s expected that a safe operation isn t possible anymore then immediately shut down device For examp...

Страница 4: ...48 7 Display LCD segment display Background lighting yes Operation 4 push buttons Ambient storage temperature 0 50 C 20 60 C max 85 non condensing eBUS x Capacity max 180 mA eBus feed 50 mA Bus line...

Страница 5: ...it must first be dismounted 1 Lift up the front cover 2 Using a screwdriver lift the controller board out of the base see the figure at the right Make sure that before begin ning wiring work all line...

Страница 6: ...nnected to the power supply in order to ensure its function at all times Upstream mains switches are there fore to be limited to emergency or main switches which are usually left in operation Before s...

Страница 7: ...irculation pump is in operation it flashes slowly In the case of the switching valves the switching state is indicates AB A or AB B and the mixer position Open or Closed MENU kWh C K INFO 1 2 3 on off...

Страница 8: ...the basic parameters 1 2 Example Change the language ENGLISH is active 3 To select DEUTSCH for example press the keys DEUTSCH will flash 4 Confirm the selection with the key You can find further infor...

Страница 9: ...06 CIRC CALIBRATION see also 8 4 Calibrating circulation volumes page 29 After start up check the following The nominal temperature values are correctly set The temperatures actual values of the conne...

Страница 10: ...ia the FRIWA pump with a speed controller which attempts to reach the set point on the TWW sensor and to hold it The TPV supply sensor for the plate heat exchanger optimizes the fresh water control si...

Страница 11: ...EG01 THERM DIS INFECT TEMP and held for the LEG02 TEMP HOLDING TIME The circulation pump is active during the protection function Sensor side B7 V2 Voltage 5 V DC Ground GND TWW sensor B6 Flow sec V1...

Страница 12: ...or providing the DHW nominal temperature value BAS01 TSET DHW plus minimal tempera ture loss STE14 MIN TDIFF HEAT EXCH on the heat exchanger The heat exchanger is held at this temperature Sensor side...

Страница 13: ...eeded at the top storage tank sensor TO1 recharging is disa bled or the heat request is ended Recharg ing can be additionally restricted via a time program Sensor side TO1 sens Tank top B7 V2 Voltage...

Страница 14: ...l mode is active 3 4 4 Test Manual mode is active Operating modes Standby AUS options DHW production still active Automatic mode The control functions are active according to the selected hydraulic ty...

Страница 15: ...RI02 Tset tank top PRI03 Tank temp bottom PRI04 Supply temperature PRI05 Return temperature SEK SECONDARY SEK01 Temperature domestic hot water SEK02 Tset domestic hot water SEK03 Temperature cold wate...

Страница 16: ...query the information in a sub menu press the key The first value will appear 5 One can navigate among the values with the key 5 6 6 The submenu selection is jumped to again by pressing the key If ano...

Страница 17: ...tion into 9 other wise carry out measurements 5 8 and then eval uate 9 Calibration successful 10 Start 11 Error Flow despite pump being switched off 12 Error Flow rate fluctuations too great with the...

Страница 18: ...setting STE07 TYPE FLOW SENSOR Attention For paddle switches no volumes are read in Here the value STE17 MAX TAPPING RATE is used and displayed SEK05 Temperature circulation Circulation temperature TB...

Страница 19: ...e ZIR12 Circ time program ZIR13 Circ mode with consumpt ZIR14 Hysteresis circulation SCH LAYERING SCH00 Return layering SCH01 Diff return layering SCH02 TU sensor type SCH03 TPR sensor type SCH04 Fix...

Страница 20: ...3 eBUS master number eBUS address of 2nd slave STN4 eBUS master number eBUS address of 3rd slave STN5 eBUS master number eBUS address of 4th slave KAS02 Sequence changeover KAS03 Station delay KAS04 C...

Страница 21: ...E ON appears and set the desired time until the next change in the switching phase with If there are multiple switching phases repeat steps 4 and 5 alternately 5 6 6 The input of switching times is ex...

Страница 22: ...e value of the adjuster can be changed with the keys The changed value is saved with the key Cancel the input or change to menu selection after the value has been set with the key By pressing once the...

Страница 23: ...ion The DHW is first heated to the set legionella protection temperature according to the setting and maintained for the minimum holding time 0 No function 15 With pump WWC and TBZ 16 With pump WWC an...

Страница 24: ...he middle part of the tank 5 40 K 25 05 105 SCH02 TU sensor type TU tank bottom sensor sensor type selection 0 NTC 5K 1 PT 1000 0 1 25 28 023 SCH03 TPR sensor type TPR PWT primary return sensor sensor...

Страница 25: ...FRIWA PP 0 100 100 0 08 088 MAN02 Circ pump speed Manual control variable Circulation pump WWC 0 100 100 0 05 122 MAN03 Return layering Manual control variable Return layering valve VSR on off off 0 0...

Страница 26: ...e entire cascade 0 Decentralized circulation pump each station has its own circulation pump settings and functions are local 1 Central circulation pump the circulation mode ther mal disinfection is se...

Страница 27: ...ses for the time STE04 RUN TIME START SPEED at the starting point in order to quickly reach the set point The primary pump speed is regulated between the minimum and maximum speed limits The maximum s...

Страница 28: ...rculation volume ZIR07 CIRCULATION FLOW RATE are defined If tapping is active and V is greater than STE15 MIN TAPPING RATE but less than ZIR08 MIN FL TAPPING SUPP circulation pump WWC is activated to...

Страница 29: ...uccessful 10 Start 11 Error Flow despite pump being switched off 12 Error Flow rate fluctuation too great with the pump switched on Calibration To calibrate ZIR07 CIRCULATION FLOW RATE a maximum of 2...

Страница 30: ...STE13 MIN CYCLING OFF TIME This way energy can be provided again on the primary side 8 6 2 Nominal value reduction Nominal value reduction This function is used when the heat source on the primary si...

Страница 31: ...perature at the top storage tank sensor TO1 is less than the current set point T1Oset minus NAC03 Recharging hysteresis recharging is enabled or heat requested If the current set point is exceeded at...

Страница 32: ...must be fallen below for a de fined time KAS03 DELAY TIME ATTENTION This should always be greater than the minimum speed of the primary pump STE03 MIN PRIM PUMP SPEED 8 9 1 Station operating mode Oper...

Страница 33: ...uence change The automatic calibration mode ZIR06 2 leads to error massages and is not recommended SCH00 RETURN LAYERING Return layering can be activated and connected locally on each device or be cen...

Страница 34: ...h stations 0 24 25 04 022 STN05 eBUS master number eBUS master numbers of the 5th stations 0 24 25 04 022 KAS02 Sequence changeover Interval sequence switching 0 8 2 06 020 KAS03 Station delay Delay t...

Страница 35: ...at OFF Check fuses set external switch to ON Wiring defective Open the controller and check the wiring Status display STA01 STATUS 5 Fault 7 Warning Jump back into title screen to read off ERRO or IN...

Страница 36: ...nsor plate heat exchanger outside of the measuring range Sensor short circuit interruption 9 2 Info message INFO Info display The controller checks the system status and signals an error This is a pla...

Страница 37: ...695 100 339 10 9 950 105 294 15 7 855 110 255 20 6 245 115 223 25 5 000 120 195 30 4 029 130 150 40 2 663 140 118 9 3 2 Resistance values PT 1000 Temperature C Resistance PT1000 Temperature C Resistan...

Страница 38: ...d PP Primary pump R RLS Return layering S Nominal value nominal Temperature specified by the operator or computed by the controller to which the heat con troller regulates the actual value T TBZ Tempe...

Страница 39: ...n heat source temperature 29 N Nominal value reduction 29 O Operation 7 14 Q Querying temperatures and operating data 16 17 R Recharging primary 13 30 Resistance values NTC 5 kOhm 36 Resistance values...

Страница 40: ...Manufacturing or Sales...

Отзывы: