4
2
Technical data
DESIGNATION/TYPE
ES 5941S
Power supply
230 V AC ± 10 % 50 – 60 HZ
Power consumption, standby
< 1 VA
Max. power consumption
5 VA
Fuse
3.15 AT
OUTPUTS (high voltage)
Electromechanical relay
5
Switching capacity
6 (2) A
Information, HE pumps
15 A - 4 s or 20 A - 0.4 s for 10 % switching duration
OUTPUTS (low voltage)
Signal output PWM or 0 - 10 V
2
INPUTS (low voltage)
Inputs, sensors
7 - NTC 5 kOHm or PT 1000, switchable
Inputs, analog (0 ... 5 V)
2 (4)
Inputs, pulse
1 (2)
HOUSING
Installation
Wall mounting
Dimensions W / H / D in mm
153.5 x 135.3 x 48.7
Display
LCD segment display
Background lighting
yes
Operation
4 push-buttons
Ambient / (storage) temperature
0 … 50 °C (- 20 ... 60 °C), max. 85 %; non-condensing
eBUS
x
Capacity
max. 180 mA
eBus feed
50 mA
Bus line – length, cross section
2-wire bus, twisted, max. 50 m, min. 0.5 mm²
TESTS/REQUIREMENTS
Degree of protection
IP 40 EN 60529
Protection class
I EN 60730-1
Safety
EN 60730-1
EMC immunity
EN 60730-1 / EN 61000-6-2
EMC emissions
EN 60730-1 / EN 61000-6-3
ErP product data
Temperature controller class / control class
-
Value
- % (contribution of the controller to seasonal space heating energy efficiency)
INFORMATION
The controller complies with the
eco-design directive
yes
TEM
Elesta
Greenline
yes ( internal voltage supply with switching power supply)