NAC04 TO sensor type
TO tank-top sensor, sen-
sor type selection
0: NTC 5K
1: PT 1000
2: 0 … 5 V
0 ... 2
-
25
28:066
NAC09 Recharging time program
Domestic water time pro-
gram
Time program for enabling domestic water production
at normal set point or to enable recharging.
-
-
-
25
05:061
KOM COMMUNICATION
KOM01 Language selection
0 ... 8
-
0
04:056
KOM03 Collective fault message
Option: Output fault mes-
sage
... here the fault messages and the info messages
could be send by this output.
-1: With an actual collective fault message no tension
is given out.
0: The function is not used.
1: With an actual collective fault message a tension is
given out.
-1;0;1
0
25
08:111
KOM04 eBUS address
eBUS addressing
Addressing the controller in the eBUS network
2 ... 16
-
25
04:020
KOM05 eBUS feed
Voltage supply of the eBUS communication, max. load
180 mA.
on/off
-
25
04:036
STE CONTROL
STE11 TPV sensor type
TPV PWT primary supply
sensor, sensor type selec-
tion
0: NTC 5K
1: PT 1000
0 ... 1
-
25
28:027
STE12 MinRuntime, cycles
Min. run-time, pri. pump,
cycle/protective function
... is active if the temperature at TPV falls below the
value TPVSet. This is for protecting the heat source
from excessive cooling. The value indicates the mini-
mum run-time or testing time during which the temper-
ature must not drop.
0 ... 180
s
25
36:025
STE13 MinOfftime, cycles
Waiting time, pri. pump, cy-
cle/protective function
... is active because TPV fell below the TPVSet value
after the minimum run-time; the pump remains disa-
bled for the set value. With this, the heat source can
increase the temperature again.
0 ... 60
min
25
36:026
MAN MANUAL
Adjusters are only active if
mode selection is set to "Manual"
.
MAN01 Prim. pump speed
Manual control variable
Primary pump (FRIWA; PP)
0 ... 100
%
100
0
08:088
MAN02 Circ. pump speed
Manual control variable
Circulation pump WWC
0 ... 100
%
100
0
05:122
MAN03 Return layering
Manual control variable
Return layering valve VSR
on/off
-
off
0
05:120
MAN04 Cascade zone valve
Manual control variable
Cascade valve ZV
on/off
-
off
0
36:020
MAN05 Recharging, primary
Manual control variable
Primary recharging request RECHRG
on/off
-
off
0
08:124
KAS CASCADE
Adjusters are only active if
Station operating mode KAS01 (36:018)
>
0 is set.
KAS01 Station operating mode
Operating mode of the sta-
tion:
0: Standalone
1: Slave
2: Master
0 ... 2
-
25
36:018
STN1 eBUS master number
eBUS master numbers of
the 1st stations
..., incl. master.
Sequence is simultaneously the activation sequence
or its start value with sequence switching active.
Value 0: Not assigned.
Input of the respective eBUS address of the station.
0 ... 24
-
25
04:022
STN2 eBUS master number
eBUS master numbers of
the 2nd stations
0 ... 24
-
25
04:022
STN3 eBUS master number
eBUS master numbers of
the 3rd stations
0 ... 24
-
25
04:022
STN4 eBUS master number
eBUS master numbers of
the 4th stations
0 ... 24
-
25
04:022
STN5 eBUS master number
eBUS master numbers of
the 5th stations
0 ... 24
-
25
04:022
KAS02 Sequence changeover
Interval sequence switch-
ing.
0: No sequence switching
1...7: After number of days
8: After each tapping
0 ... 8
-
25
06:020
KAS03 Station delay
Delay time
Minimum dwell time of primary pump control variable
at the upper or lower switching threshold.
0 ... 180
s
25
36:019
KAS04 Cas. switch-off threshold
Lower switching point
... for switching off the last or currently active station in
the cascade
0 ... 100
%
25
36:021
KAS05 Cas. switch-on threshold
Upper switching point
... for activating new stations in the cascade
0 ... 100
%
25
36:022
The visible values vary depending on the selected hydraulic variant, as well as option, and depend on the input password, "Key" column.
Menu
Description
Range
Unit
Value
Key
ID