24
ZIR06 Circ. calibration
Circulation flow calibration 0:
Off
= No calibration
1:
Manual
= Calibrate 1x.
No automatic reset to 0. For re-calibration, set to 0 and
then to 1.
2:
Auto
= calibrate every Monday at 2 a.m.
0 ... 2
-
25
36:010
ZIR07 Circulation flow rate
Circulation flow
Flow for active circulation pump as manual input of as
instrumentally determined value from ZIR06 Circ. Cal-
ibration.
0 ... 999.9
l/min
25
23:111
ZIR10 Circ. pulse run-time
Min. WWC run-time
If the circulation pump is operated with pulse control,
the run-time of the WWC pump is defined with this val-
ue. This minimum run-time is also valid for tapping
support.
0 ... 30
min
25
05:070
ZIR11 Circ. pulse off-time
WWC off-time
After the run-time ZIR11 circ. pulse run-time (05:070)
of the WWC pump has elapsed, the operation of the
WWC is disabled by this time. This minimum down-
time is also valid for tapping support.
0 ... 240
min
25
05:071
ZIR12 Circ.time program
DHW circulation time pro-
gram
Time program for enabling the circulation function
-
-
-
0
05:064
ZIR13 Circulation mode with con-
sume
Circulation mode with con-
sume
... defines if the selected circulation mode is active with
consumation or not. Note: the consumer support is in-
dependet always active.
0: on - Circulation mode is active with consumption
1: off - Circulation mode is inactive with consumption
0 ... 1
-
-
25
36:032
ZIR14 Hysteresis circulation
Switching ON hysteresis
for setpoint temp. circula-
tion
If the circulation return temperature falls below of the
the circulation setpoint temperature minus the set-
point, the circulation pump is switched on.
-
-
-
0
05:064
SCH Layering
Adjuster visible If return layering SCH00 is set unequal 0.
SCH00 Return layering
Option: Return layering
on / off
off
0
05:110
SCH01 Diff. RET layering
Switch-off boost for return
layering, SRD TOP
Switch-off difference between bottom buffer TUx and
return temperature of primary-side heat exchanger
TPR.
TPR > T1U + SRD top = USR OFF (return is charged
in the middle part of the tank)
5 ... 40
K
25
05:105
SCH02 TU sensor type
TU tank-bottom sensor,
sensor type selection
0: NTC 5K
1: PT 1000
0 ... 1
-
25
28:023
SCH03 TPR sensor type
TPR PWT primary return
sensor, sensor type selec-
tion
0: NTC 5K
1: PT 1000
0 ... 1
-
25
28:028
SCH04 Fix value TU1 tank bottom Replacement value sensor
tank bottom
Fixed value for the tank bottom sensor, if no sensor
can be connected. If a sensor is connected, the value
has to be 120 °C.
0 ... 120
°C
0
28:083
LEG Therm. Disinfection
Adjuster visible if
Therm. Disinfection BAS04
(05:014) set not equal to 0.
LEG00 Therm. disinfection
Function thermical desinfection
0 ... 18
-
0
05:014
LEG01 Therm.disinfect. temp.
Thermal disinfection set
point
(Legionella protection). Is valid when thermal disinfec-
tion is enabled.
60 ... 80
°C
0
05:004
LEG02 Temp. holding time,
.thm.dis
Min. holding time, thermal
disinfection nominal tem-
perature value
With this adjuster, it is defined how long the nominal
value is held for therm. disinfection so that the le-
gionella protection is ended successfully.
0 ... 480
min
0
05:043
LEG03 TSET hysteresis, thm.dis
Charging boost for therm.
Disinfection
Boost of the DHW set point in thermal disinfection
mode. To take the thermal losses in the system into
account, so that the temperature 05:004 LegioSet can
also be reached at the reference sensor.
0 ... 30
K
25
36:024
LEG04 Man. Therm.disinfect.
Thermal disinfection, man-
ual
on/off
-
25
05:084
LEG05 Thm.Disinf.Time.program
Thermal disinfection time
program
Time program for enabling the legionella protection
function
-
-
-
25
05:062
NAC Recharging
Adjuster visible if
Primary recharging NAC00
(08:100) or
Secondary recharging BAS10
(05:114) is set to "on".
NAC00 Recharging primary
Option: termical recharging demand
on / off
off
0
08:110
NAC03 Recharging hysteresis
Switch-on hysteresis for
set tank temperature
If the temperature in the tank < set point minus this set
value, there will be a charging request (internal func-
tion / heat management).
1 ... 30
K
0
08:063
The visible values vary depending on the selected hydraulic variant, as well as option, and depend on the input password, "Key" column.
Menu
Description
Range
Unit
Value
Key
ID