background image

17

7.3.1

 Adapting the standard display

Accept value on standard display:

Select the measured temperature or data value to be accepted as described in sect. 7.3, 
page 16
. Keep the 

 key pressed until "YES" appears on the display. The value is 

shown on the standard display. 

7.3.2

 Resetting energy data

Reset energy in kWh:

The energy can be reset manually. The current value is set to zero by pressing the 

 

key for a few seconds. If the 

 key is pressed, the display in kWh is reset to "0" again.

7.4

Values on information level

INFO

The visible values vary depending on the selected hydraulic variant, as well as the option, and depend on the input password, "Key" column; 

see sect. 7.6, page 20.

Menu

Description

Range

Unit

Value

Key

ID

INFO

STA STATUS

STA01 Status

Status of the DHW produc-
tion

0 : Switched off 
2 : Thermal disinfection / comfort mode 
5 : Fault
6 : Tapping/ DHW withdrawal
7 : Warning
8 : Nominal value reduction
10 : Reheating
11 : Cancel charging
14 : Standby station in cascade

0 ... 11

-

-

0

02:052

STA02 Circ. Calibration

Status of circulation flow 
calibration

0:     Inactive

 

Calibration not done yet or last calibration obso-
lete.

1..8: Active, measurements 1..8.

 

If measurements 1..4 OK, transition into 9; other-
wise, carry out measurements 5..8 and then eval-
uate. 

9:     Calibration successful.
10:   Start.
11:   Error - Flow despite pump being switched off.
12:   Error - Flow rate fluctuations too great with the 

pump switched on.

0

STA03 Thm.disinfection info

Information about thermal 
disinfection

... with time specified when this was successfully car-
ried out.

yyyy 

dd:mm

-

-

0

02:127

STA04 Speed, pri. pump

Current control variable

Output 1

0 ... 100

%

-

0

22:031

STA05 Output, circ. pump

Current control variable

Output 2

0 ... 100

%

-

0

22:032

STA06 Current control variable A3 Current control variable

Output 3

0 ... 100

%

-

0

22:033

STA07 Current control variable A4 Current control variable

Output 4

0 ... 100

%

-

0

22:034

STA08 Current control variable A5 Current control variable

Output 5

0 ... 100

%

-

0

22:035

STN1 Station casc. status

Status during cascade op-
eration

... of the station in the FW cascade manager:
Digit 1:       
Sequence number of the station, range 0..5,
0: Station not available

Digits 2..4: Control signal s of the KM for this station:
 0: Off
 1..100: Override with s%
 101: Not ready, no energy
 102: Standby
 103: Control

00 ... 1103

-

-

0

02:123

STN2 Station casc. status

Status during cascade op-
eration

00 ... 2103

-

-

0

STN3 Station casc. status

Status during cascade op-
eration

00 ... 3103

-

-

0

STN4 Station casc. status

Status during cascade op-
eration

00 ... 4103

-

-

0

STN5 Station casc. status

Status during cascade op-
eration

00 ... 5103

-

-

0

Содержание TACOTHERM FRESH PETA ES 5941S

Страница 1: ...ova Group AG Neunbrunnenstrasse 40 CH 8050 Zurich T 41 44 735 55 55 F 41 44 735 55 02 group taconova com 03 2017 Art Nr 212788 EA Nr 1243 en CONTROLLER MANUAL TACOTHERM FRESH PETA FRESH HOT WATER STAT...

Страница 2: ...mode 14 7 2 INFO parameter overview 15 7 3 Querying temperatures and operating data 16 7 4 Values on information level 17 7 5 Parameters MENU overview 19 7 6 Enter password 20 7 7 Clock program 21 7...

Страница 3: ...underground Never run device above or below limit values as listed under the technical data When it s expected that a safe operation isn t possible anymore then immediately shut down device For examp...

Страница 4: ...48 7 Display LCD segment display Background lighting yes Operation 4 push buttons Ambient storage temperature 0 50 C 20 60 C max 85 non condensing eBUS x Capacity max 180 mA eBus feed 50 mA Bus line...

Страница 5: ...it must first be dismounted 1 Lift up the front cover 2 Using a screwdriver lift the controller board out of the base see the figure at the right Make sure that before begin ning wiring work all line...

Страница 6: ...nnected to the power supply in order to ensure its function at all times Upstream mains switches are there fore to be limited to emergency or main switches which are usually left in operation Before s...

Страница 7: ...irculation pump is in operation it flashes slowly In the case of the switching valves the switching state is indicates AB A or AB B and the mixer position Open or Closed MENU kWh C K INFO 1 2 3 on off...

Страница 8: ...the basic parameters 1 2 Example Change the language ENGLISH is active 3 To select DEUTSCH for example press the keys DEUTSCH will flash 4 Confirm the selection with the key You can find further infor...

Страница 9: ...06 CIRC CALIBRATION see also 8 4 Calibrating circulation volumes page 29 After start up check the following The nominal temperature values are correctly set The temperatures actual values of the conne...

Страница 10: ...ia the FRIWA pump with a speed controller which attempts to reach the set point on the TWW sensor and to hold it The TPV supply sensor for the plate heat exchanger optimizes the fresh water control si...

Страница 11: ...EG01 THERM DIS INFECT TEMP and held for the LEG02 TEMP HOLDING TIME The circulation pump is active during the protection function Sensor side B7 V2 Voltage 5 V DC Ground GND TWW sensor B6 Flow sec V1...

Страница 12: ...or providing the DHW nominal temperature value BAS01 TSET DHW plus minimal tempera ture loss STE14 MIN TDIFF HEAT EXCH on the heat exchanger The heat exchanger is held at this temperature Sensor side...

Страница 13: ...eeded at the top storage tank sensor TO1 recharging is disa bled or the heat request is ended Recharg ing can be additionally restricted via a time program Sensor side TO1 sens Tank top B7 V2 Voltage...

Страница 14: ...l mode is active 3 4 4 Test Manual mode is active Operating modes Standby AUS options DHW production still active Automatic mode The control functions are active according to the selected hydraulic ty...

Страница 15: ...RI02 Tset tank top PRI03 Tank temp bottom PRI04 Supply temperature PRI05 Return temperature SEK SECONDARY SEK01 Temperature domestic hot water SEK02 Tset domestic hot water SEK03 Temperature cold wate...

Страница 16: ...query the information in a sub menu press the key The first value will appear 5 One can navigate among the values with the key 5 6 6 The submenu selection is jumped to again by pressing the key If ano...

Страница 17: ...tion into 9 other wise carry out measurements 5 8 and then eval uate 9 Calibration successful 10 Start 11 Error Flow despite pump being switched off 12 Error Flow rate fluctuations too great with the...

Страница 18: ...setting STE07 TYPE FLOW SENSOR Attention For paddle switches no volumes are read in Here the value STE17 MAX TAPPING RATE is used and displayed SEK05 Temperature circulation Circulation temperature TB...

Страница 19: ...e ZIR12 Circ time program ZIR13 Circ mode with consumpt ZIR14 Hysteresis circulation SCH LAYERING SCH00 Return layering SCH01 Diff return layering SCH02 TU sensor type SCH03 TPR sensor type SCH04 Fix...

Страница 20: ...3 eBUS master number eBUS address of 2nd slave STN4 eBUS master number eBUS address of 3rd slave STN5 eBUS master number eBUS address of 4th slave KAS02 Sequence changeover KAS03 Station delay KAS04 C...

Страница 21: ...E ON appears and set the desired time until the next change in the switching phase with If there are multiple switching phases repeat steps 4 and 5 alternately 5 6 6 The input of switching times is ex...

Страница 22: ...e value of the adjuster can be changed with the keys The changed value is saved with the key Cancel the input or change to menu selection after the value has been set with the key By pressing once the...

Страница 23: ...ion The DHW is first heated to the set legionella protection temperature according to the setting and maintained for the minimum holding time 0 No function 15 With pump WWC and TBZ 16 With pump WWC an...

Страница 24: ...he middle part of the tank 5 40 K 25 05 105 SCH02 TU sensor type TU tank bottom sensor sensor type selection 0 NTC 5K 1 PT 1000 0 1 25 28 023 SCH03 TPR sensor type TPR PWT primary return sensor sensor...

Страница 25: ...FRIWA PP 0 100 100 0 08 088 MAN02 Circ pump speed Manual control variable Circulation pump WWC 0 100 100 0 05 122 MAN03 Return layering Manual control variable Return layering valve VSR on off off 0 0...

Страница 26: ...e entire cascade 0 Decentralized circulation pump each station has its own circulation pump settings and functions are local 1 Central circulation pump the circulation mode ther mal disinfection is se...

Страница 27: ...ses for the time STE04 RUN TIME START SPEED at the starting point in order to quickly reach the set point The primary pump speed is regulated between the minimum and maximum speed limits The maximum s...

Страница 28: ...rculation volume ZIR07 CIRCULATION FLOW RATE are defined If tapping is active and V is greater than STE15 MIN TAPPING RATE but less than ZIR08 MIN FL TAPPING SUPP circulation pump WWC is activated to...

Страница 29: ...uccessful 10 Start 11 Error Flow despite pump being switched off 12 Error Flow rate fluctuation too great with the pump switched on Calibration To calibrate ZIR07 CIRCULATION FLOW RATE a maximum of 2...

Страница 30: ...STE13 MIN CYCLING OFF TIME This way energy can be provided again on the primary side 8 6 2 Nominal value reduction Nominal value reduction This function is used when the heat source on the primary si...

Страница 31: ...perature at the top storage tank sensor TO1 is less than the current set point T1Oset minus NAC03 Recharging hysteresis recharging is enabled or heat requested If the current set point is exceeded at...

Страница 32: ...must be fallen below for a de fined time KAS03 DELAY TIME ATTENTION This should always be greater than the minimum speed of the primary pump STE03 MIN PRIM PUMP SPEED 8 9 1 Station operating mode Oper...

Страница 33: ...uence change The automatic calibration mode ZIR06 2 leads to error massages and is not recommended SCH00 RETURN LAYERING Return layering can be activated and connected locally on each device or be cen...

Страница 34: ...h stations 0 24 25 04 022 STN05 eBUS master number eBUS master numbers of the 5th stations 0 24 25 04 022 KAS02 Sequence changeover Interval sequence switching 0 8 2 06 020 KAS03 Station delay Delay t...

Страница 35: ...at OFF Check fuses set external switch to ON Wiring defective Open the controller and check the wiring Status display STA01 STATUS 5 Fault 7 Warning Jump back into title screen to read off ERRO or IN...

Страница 36: ...nsor plate heat exchanger outside of the measuring range Sensor short circuit interruption 9 2 Info message INFO Info display The controller checks the system status and signals an error This is a pla...

Страница 37: ...695 100 339 10 9 950 105 294 15 7 855 110 255 20 6 245 115 223 25 5 000 120 195 30 4 029 130 150 40 2 663 140 118 9 3 2 Resistance values PT 1000 Temperature C Resistance PT1000 Temperature C Resistan...

Страница 38: ...d PP Primary pump R RLS Return layering S Nominal value nominal Temperature specified by the operator or computed by the controller to which the heat con troller regulates the actual value T TBZ Tempe...

Страница 39: ...n heat source temperature 29 N Nominal value reduction 29 O Operation 7 14 Q Querying temperatures and operating data 16 17 R Recharging primary 13 30 Resistance values NTC 5 kOhm 36 Resistance values...

Страница 40: ...Manufacturing or Sales...

Отзывы: