4.8 Connect drainage pipe
Personnel:
n
Technicians for sanitary, heating and
air conditioning engineering systems
Protective equip-
ment:
n
Safety shoes
n
Safety gloves
n
Ear protection
n
Occupational safety clothing (Personal
Protection Equipment - PPE)
If a compression refrigeration system is assembled in the device
and a drainage pipe line is installed outside the device, the
drainage pipe must be connected and guided to a safe area. The
drainage pipe is marked with a symbol (Fig. 33).
1.
Connect a 22-mm copper pipe to the connection of the
drainage pipe.
2.
The client must guide the drainage pipe for the refrigerant
into an area which is not at risk (e.g. outgoing air duct). No
shut-off device may be assembled.
3.
Protect the end of the pipe from soiling with a loose cap.
Fig. 33: Drainage pipe
Connect drainage pipe
25.08.2022
Device type: Menerga TX - ThermoCond
42