8.
Check that all terminals are firmly fastened and, if necessary,
retighten.
NOTICE!
When performing the high voltage test, assemblies
or devices that are not dimensioned for the high
voltage test or have already been tested using
the corresponding product standard, have to be
disconnected before the high voltage test.
9.
Conduct protective earth conductor, insulation resistance and
high voltage test according to EN 60204 (VDE 0113) in com-
pliance with the necessary safety precautions.
10.
Block all flange holes on the control cabinet and in the device
that are not used with blind plugs.
4.10 After the installation
Personnel:
n
Technicians for sanitary, heating and
air conditioning engineering systems
Protective equip-
ment:
n
Safety shoes
n
Safety gloves
n
Ear protection
n
Occupational safety clothing (Personal
Protection Equipment - PPE)
The unit must be commissioned by the manufac-
turers employees or by personnel authorised by
the manufacturer.
1.
Remove tools and materials completely from the unit.
2.
Clean the inside of the unit.
3.
Insert filter into the filter guides.
4.
Attach all covers.
After the installation
25.08.2022
Device type: Menerga TX - ThermoCond
45