6.
Flush the water circuit with water before filling the water cir-
cuit.
7.
Fasten the temperature sensors (Fig. 31/6 and 7) at the des-
ignated point in the pipelines. Use roller springs (included in
the scope of delivery) to do so. Apply thermal paste between
the pipeline and sensor. Ensure a tight fit. Install insulation
Ensure that the sensors are under the insulation.
8.
Fill the water circuit according to the technical data sheet of
the respective heat transfer media. See the technical data in
the
Ä
“
Operating manual
”
.
9.
If the heat exchanger is not bled, then the
performance will be reduced and may mal-
function.
Bleed the heat exchanger with the aid of the bleeder valve
assembled at the highest point.
10.
Check the connections and the heat exchanger in the device
for leaks.
11.
Insulate the pipes according to the markings in the building
heat pump circuit (Fig. 30).
12.
Securely mount the enclosure for the temperature sensors in
a suitable location. Connect all sensors and actuators to the
control cabinet as per the circuit diagram.
Connecting the building heat pump
25.08.2022
Device type: Menerga TX - ThermoCond
40