5.10. Battery Setup Page
To configure battery settings, click on the BATTERY icon and then on ‘Batt type’.
What this page displays:
Battery capacity in (Ah) – For non-BMS-batteries the range allowed is 0-2000Ah, while for
lithium-ion the inverter will user the capacity value of the BMS.
Max battery charge current (Amps).
Max battery discharge current (Amps), which should be 20% of the Ah rating for AGM only.
For Lithium, please refer to the battery manufacturer documentation. Note: This is a global
max. discharge current for both ‘grid-tied’ and ‘backup’ modes of operation and if the cur-
rent exceeds this value inverter will shut down with an overload fault.
TEMPCO settings - Temperature coefficient is the error introduced by a change in tempera-
ture.
What you can do from this page:
Use battery voltage for all settings (V).
Use battery SOC for all settings (%).
No battery: tick this box if no battery is connected to the system.
BMS setting.
Active battery - This feature will help recover a battery that is 100% discharged by slowly
changing from the solar array. Until the battery reaches a point where it can change normally.
Содержание SUN-25K-SG01HP3-EU-BM2
Страница 19: ...Page 19 Hybrid Inverter Installer Manual 4 4 1 Function Ports Definition ...
Страница 26: ...Page 26 Hybrid Inverter Installer Manual ...
Страница 27: ...Page 27 Hybrid Inverter Installer Manual ...
Страница 29: ...Page 29 Hybrid Inverter Installer Manual 4 10 Wiring System for Inverter ...
Страница 30: ...Page 30 Hybrid Inverter Installer Manual 4 11 Wiring Diagram ...
Страница 31: ...Page 31 Hybrid Inverter Installer Manual ...
Страница 32: ...Page 32 Hybrid Inverter Installer Manual 4 12 Typical Application Diagram of Diesel Generator ...
Страница 33: ...Page 33 Hybrid Inverter Installer Manual 4 13 Three Phase Parallel Connection Diagram 01 02 03 ...
Страница 44: ...Page 44 Hybrid Inverter Installer Manual ...
Страница 68: ...Page 68 Hybrid Inverter Installer Manual 5 23 3 MODE III With Smart Load 5 23 4 MODE IV AC Couple ...