Page | 17
Hybrid Inverter | Installer Manual
4.4. Battery Connection
For safe operation and compliance, an individual DC overcurrent protector or disconnection
device is required for the connection of the battery and the inverter. Users are recommended to
utilise a suitable fuse and DC isolator (see next page). In some applications, switching devices
may not be required, but overcurrent protectors must be used. Please refer to the typical am-
perage in the table below for the required fuse or circuit breaker size.
Please follow below steps to implement battery connection:
1. Pass the cable through the terminal:
Reverse Polarity
All wiring/connecting must be performed by qualified personnel. Before making
the final DC connection or closing the DC Breaker/disconnection device, ensure
the inverter unit is wired correctly. A reverse-polarity connection on the battery will
damage the inverter.
Model
Cross section (mm
2
)
Range
Recommended value
25/30/40/50KW
16.0~25.0 (6~4AWG)
16.0(6AWG))
2. Put on the rubber ring:
Содержание SUN-25K-SG01HP3-EU-BM2
Страница 19: ...Page 19 Hybrid Inverter Installer Manual 4 4 1 Function Ports Definition ...
Страница 26: ...Page 26 Hybrid Inverter Installer Manual ...
Страница 27: ...Page 27 Hybrid Inverter Installer Manual ...
Страница 29: ...Page 29 Hybrid Inverter Installer Manual 4 10 Wiring System for Inverter ...
Страница 30: ...Page 30 Hybrid Inverter Installer Manual 4 11 Wiring Diagram ...
Страница 31: ...Page 31 Hybrid Inverter Installer Manual ...
Страница 32: ...Page 32 Hybrid Inverter Installer Manual 4 12 Typical Application Diagram of Diesel Generator ...
Страница 33: ...Page 33 Hybrid Inverter Installer Manual 4 13 Three Phase Parallel Connection Diagram 01 02 03 ...
Страница 44: ...Page 44 Hybrid Inverter Installer Manual ...
Страница 68: ...Page 68 Hybrid Inverter Installer Manual 5 23 3 MODE III With Smart Load 5 23 4 MODE IV AC Couple ...